Part 8
Unlocking a C•CURE door on DTMF
Activation
The integ
ration may be configured to trigger a C•CURE door to open when a DTMF code is sent to the
device. To configure such an action, carry out the following steps:
1.
Open a 2N intercom to edit in C•CURE.
2.
Ensure the correct DTMF code required is configured on the General tab for the intercom.
3.
Go to the Triggers tab and click Add.
4.
Configure the Trigger columns as follows:
a.
Property
–
DTMF State
b.
Value
–
Activated
c.
Action
–
Unlock Door Action
d.
Details
–
(select the C•CURE door you wish to trigger the open action on
from the
bottom field)
5.
Save the configuration.
NOTE
DTMF Activation is supported on physical doors configured in
C•CURE only. Simulated
doors are not supported for DTMF actions. Please ensure the iSTAR Driver Service is
running on the C•CURE server if you wish to use this feature.
When the DTMF code is entered on the Master station, this will trigger a Momentary Unlock action for
the C•CURE door
, shown in the journal:
If an incorrect DTMF code is entered into the Master Station, this will also be journaled and the door will
not be opened: