HW Settings
Mode
Select required ventilation mode
DCV
- Ventilation according to the requirements of the air
quality sensor (AQS)
•
Unit ventilates at the air quality sensor (AQS) require
-
ments, e.g. CO2, RH (sensor control signal must range
from 0-10V).
CAV
- manual ventilation mode
•
Unit ventilates at the selected power independent of the
AQS
VAV
- variable air volume - constant pressure in the supply
duct
•
The unit changes the flow rate to the total opening or clo
-
sing of VAV dampers in the supply ducts (done in the case
of ventilation multiple zones with individual requirements
for ventilation intensity - each zone is equipped with inlet
control VAV flap = separate independent control circuit)
The Software reset (menu 48) must be performed to save
the changes
In this menu you can set the logic of using the RUN contact
and the logic of antifreeze protection
02
01
1
2
1. RUN contact settings
This menu lets you select the logic using with the RUN
output. Imput (7-8) - The logic of the connected RUN
contact can be set as follows: as N. close (normally clo
-
sed) or N. Open (normally open)
2. Setting the logics of the behaviour of the exhaust fan
during active antifreeze protection