HW test

18

The HW TEST menu is used to test all the connected com-

ponents and accessories. These parameters are not saved. 

F in

 - Intake fan speed configuration 

F out

 - Exhaust fan speed configuration

Pre 1

 - Electric preheating power configuration

    

(intake fan automatically activated)

Ext1

 -  Intake air temperature sensor (fresh air supply)

Ext3

 -  Air intake temperature sensor (inlet to room)

Int1

 -  Exhaust air temperature sensor (exhaust before core)

Int2

 -  Anti-freeze sensor of the heat exchanger

    

(exhaust behind core)

Summary of Contents for AirGENIO

Page 1: ...PCB MODULE A AirGENIO CONN CABLE UTP AirGENIO PWR SOURCE 24VCD AirGENIO TEMP SENSOR 3 2M AirGENIO CONTROL PANEL AirGENIO PCB MODULE B AirGENIO TEMP SENSOR 10M AirGENIO PRESSURE LP AirGENIO PCB MODULE G AirGENIO I BUS 300MM AirGENIO PRESSURE HP AirGENIO PCB MODULE GL AirGENIO PCB SUPPORT AirGENIO PRESSURE VHP AirGENIO PCB MODULE K Package contents Qty Package contents Qty Package contents Qty NOTE ...

Page 2: ...bols on the screen Start up The unit is launched by pushing the red circle symbol 1 Turn the unit ON OFF 2 BOOST mode activation 3 Unit s time switch 4 Password lock 5 Ventilation mode settings 6 Required temperature settings 7 Detailed informationof ventilation status 8 Settings 9 Display of current temperature ventilation rate CO2 com centration ventilation mode and date 1 Night cooling 2 Occupa...

Page 3: ...sor 1 Back 2 Information about unit type The BOOST mode is activated by touching symbol BOOST regime is displayed in ventilantion mode area 1 2 UNIT SETTINGS 4 1 2 3 5 6 7 8 1 Date and time 2 Display settings 3 Language settings 4 Ventialtion level settings 5 AirGENIO application 6 QR code with contact details and technical sheet download link 7 Unit s service setting 8 Required temperature settin...

Page 4: ...ducing or increasing required temperature in the range from 15 C to 45 C REQUIRED TEMPERATURE SETTINGS UNIT S TIME SWITCH 1 2 3 1 1 Actiavtion deactivation of time switch 2 Week regime 3 Year regime 2 3 Touch a day to set ventilation modes Week mode Touch to set individual intervals of ventilation time ON OFF vent mode vent level temperature 1 Touch for copying time interval 1 ...

Page 5: ...sired temperature and fan power In automatic mode only the desired temperature may be set Fan power is driven using AQS 1 Beginning of time interval Day Month 2 End of time interval Day Month 3 Values setting 4 Delete time interval 5 Back When the time interval ends the unit goes into stand by mode Add a time mode 2 4 3 5 1 LANGUAGE SETTINGS ...

Page 6: ...6 2VV Creating innovative solutions for you and your business since 1995 ver 1 07 04 20 DISPLAY SETTINGS 1 Display brightness in active mode 2 Display brightness in Standby mode 2 1 ...

Page 7: ...ving the unit to the app AirGENIO APP 1 QR code for downloading the AirGENIO application for smart devices 2 Pairing mobile device with unit using QR code The IP address and PIN of the unit can be entered manually or by using a QR code for quick pairing of the unit 1 1 2 Press Google Play icon or App Store icon depending on your device type to get the app download or find it manualy in the store ...

Page 8: ...mart device manual pairing with the unit 1 Enter the IP address from controller 2 Enter the PIN from the controller 3 Name the unit 4 Select language 5 After entering all the information from the controller press Save for saving the unit to the app Scroll down to the Network section 1 2 3 4 5 ...

Page 9: ...to set the date and time Use code 1616 to access the service MENU This MENU is intended primarily for service technicians or users who have experience with HVAC units Changes in this MENU can lead to improper operation of the unit If you are uncertain first contact your supplier for more information 1616 Scroll up down to select menu then tap on selected menu ...

Page 10: ...tal opening or clo sing of VAV dampers in the supply ducts done in the case of ventilation multiple zones with individual requirements for ventilation intensity each zone is equipped with inlet control VAV flap separate independent control circuit The Software reset menu 48 must be performed to save the changes In this menu you can set the logic of using the RUN contact and the logic of antifreeze...

Page 11: ...ed During the calibration the unit determines the maximum pressure loss when the fan runs at full rate READ CAREFULLY The unit will not work properly if du ring calibration the distribution network is not complete the flaps or valves are not closed etc Fan calibration Accessories 04 03 Select optional accessories The Software reset menu 48 must be performed to save the changes ...

Page 12: ...ed out during the first commi ssioning and after a filter class change This menu serves to set the second additional preheater or post heater Filter calibration Exchangers 05 07 Postheater None Electric Water WCO DX The Software reset menu 48 must be performed to save the changes Preheating not for HR85 None Electric Water ...

Page 13: ...red limits setting AQS Air Quality Sensor BREATHING with the breathing mode enabled the unit shuts down after reaching the minimum concentration and then inhales every 15 minutes for 2 minutes at minimum fan power If the con centration exceeds the maximum value ventilation is reacti vated If the max Limit is not exceeded the unit switches off again until the next inhalation The Software reset menu...

Page 14: ...he outlet channel adjust the limit and change the sensor to the supply the MIN value will be respected according to the settings Extract duct The unit will be controlled by the extract air temperature sensor from the object Suitable for installations where it is necessary to monitor the average exhaust air temperature and adjust the supply air temperature to achieve comfort in the building Suitabl...

Page 15: ...ture range of 25 C to 45 C 3 Set minimum canal temperature range of 15 C to 20 C Due to possible condensation on the surface of the ven tilation ductwork it is recommended to leave enabled the reduction of flow if canal minimum is not reached Selecting the sensor in the supply ductwork disables the maximum temperature setting in the ductwork 1 2 3 Setting of minimum outdoor temperature from which ...

Page 16: ... motor for the intake branch will be activated Exhaust only flow only the motor for the exhaust branch will be activated 2 Setting the airflow when the FIRE contact opens input terminals15 16 FIRE VENTILATION input has highest priority it deacti vates all other modes including anti frost protection 08 08 Flow Offset Fire Flow 12 13 Setting underpressure or overpressure 0 equal pressure positive va...

Page 17: ...y mode but will remain active The unit will work at the value set prior to its transition into Standby mode 1 Setting the time interval for which the mode will be active after the BOOST contact is activated 2 Setting the required airflow Boost can be activated with the button connected to the input 13 14 or with the Boost button Fig Boost on main screen 1 Setting the time interval after which the ...

Page 18: ...ctivation of NIGHT VENTILATION NIGHT VENTILATION is evaluated even if the unit is in Standby mode at the selected date and time the unit acti vates and evaluates where night ventilation can be activated Prefreecooling NIGHT VENTILATION does not replace an air conditio ning unit The primary purpose of the unit is to ventilate not to cool Setting the regulation characteristics If regulation is varia...

Page 19: ...ters are not saved F in Intake fan speed configuration F out Exhaust fan speed configuration Pre 1 Electric preheating power configuration intake fan automatically activated Ext1 Intake air temperature sensor fresh air supply Ext3 Air intake temperature sensor inlet to room Int1 Exhaust air temperature sensor exhaust before core Int2 Anti freeze sensor of the heat exchanger exhaust behind core ...

Page 20: ...n Off On Off switching 0 10V signal control cooling heating 10 0V CH 10 0V Off On Off On switching 0 10V signal control cooling heating 10 0V 08 DX exchanger 19 1 Min power for switching the heat pump 2 Upper output limit 0 10V of HEATER COOLER output for requirement state of 0 capacity of the condensing unit default 1V 3 Max number of activations of the condensing unit in ON OFF mode per hour ran...

Page 21: ...since 1995 ver 1 07 04 20 08 Network 21 The NETWORK menu serves for setting the network commu nications of the unit TCP Modbus The Software reset menu 48 must be performed to save the changes 08 Modbus RTU 20 The MODBUS menu is used to set the Modbus communica tion ...

Page 22: ...t without password Activate Deactivate Temperature Flow Enables activa tion and deactivation of the unit setting required temperature and ventilation power without password Temperature Flow Enables setting the desired temperatu re and ventilation power without password Full Does not enable any settings without entering password User mode Enables the unit to be operated per the following screen Aft...

Page 23: ...VV Creating innovative solutions for you and your business since 1995 ver 1 07 04 20 The BACnet menu is used to set the unit s network commu nication ModBus TCP Power reset 08 08 BACnet Software reset 38 48 ...

Page 24: ... to its factory settings does not change the configuration AQS ventilation mode HW settings temperature settings Modbus settings 1 Controller address only if two controllers connected This setting is saved in each controller separately CP1 Address 1 CP2 Address 2 2 Summer time enabled disabled 3 Switch off the rotary heat exchanger no heat recovery for HR85 only 1 2 3 ...

Page 25: ...ing indicator is located on the control display panel The clogging of the filters is automatically assessed The unit will automatically recognize that a new filter has been installed ATTENTION In case that filters will not be replaced properly func tionality of the unit may be reduced the preheater can overheat and ventilator can be damaged ...

Page 26: ... failure T EXT1 unit is ventilating Defective contact or sensor Control the connection of the sensor and replace if needed professional service 17 Inlet Failure of the temperature sensor behind the exchanger T EXT2 unit is ventilating Defective contact or sensor Control the connection of the sensor and replace if needed professional service 18 Inlet Temperature sensor failure in the supply canal T...

Page 27: ...ed read carefully the safe operation manual of the unit That manual includes examples of possible problems and recommended solutions In case of any requests or inquiries contact our sales or technical department CONTACT Address 2VV s r o Fáblovka 568 533 52 Pardubice Czech Republic Website http www 2vv cz CONCLUSION i ...

Reviews: