8
9
2VV.
Creating innovative solutions for you and your business since 1995.
ver.5 5-05-20
5. TECHNICAL PARAMETERS
Ventilator parameters
(for 1 ventilator)
Type
Number of
phases
Voltage
[V]
Frequency
[Hz]
Power consumption
[W]
Current
[A]
Speed
[rpm]
Operating
temperature
min.
[°C]
Operating
temperature
max.
[°C]
HR95-080EC-..-....
1
230
50
175
1,3
2800
-25
60
HR95-150EC-..-....
1
230
50
455
3,1
2600
-25
40
HR95-250EC-..-....
1
230
50
500
3,15
1970
-25
60
HR95-350EC-..-....
3
400
50
1000
1,75
2140
-25
50
HR95-450EC-..-....
3
400
50
1000
1,75
2140
-25
50
HR95-550EC-..-....
3
400
50
1615
2,5
1750
-25
50
Electric preheater parameters
Type
Number of
phases
Voltage
[V]
Frequency
[Hz]
Power consumption
[W]
Current
[A]
HR95-080..-..-..E.
1
230
50
2700
11,8
HR95-150..-..-..E.
3
400
50
5300
13,3
HR95-250..-..-..E.
3
400
50
8300
12,0
HR95-350..-..-..E.
3
400
50
11700
16,9
HR95-450..-..-..E.
3
400
50
15000
21,7
HR95-550..-..-..E.
3
400
50
18300
26,5
Electric reheater parameters
Type
Air flow
[m³/h]
Air heating
[°C]
Total power
[kW]
Current
[A]
Number of
phases
Voltage [V]
HR95-080..-..-...E
650
6,3
1,4
6,1
1
230
HR95-150..-..-...E
1500
5,3
2,7
11,8
1
230
HR95-250..-..-...E
2250
6,3
4,8
6,9
3
400
HR95-350..-..-...E
3500
5,4
6,4
9,3
3
400
HR95-450..-..-...E
4500
5
7,6
11
3
400
HR95-550..-..-...E
5500
5,7
10,6
15,4
3
400
Hot-water reheater parameters
Type
Air flow
[m³/h]
Power
(kW)*
Temperature
after exiting
the heater
[°C]
Pressure
drop in the
water flow
[kPa]
Pressure
drop in the
air flow
[Pa]
Connection
cross-section [
„
]
HR95-080..-..-...W
650
2,88
28,2
4
13
1/2“
HR95-150..-..-...W
1500
5,44
25,8
3
25
1/2“
HR95-250..-..-...W
2250
9,73
27,9
11
27
1/2“
HR95-350..-..-...W
3500
14,1
27,9
10
18
1/2“
HR95-450..-..-...W
4500
16
26,1
4
22
1/2“
HR95-550..-..-...W
5500
22,7
27,3
7
22
3/4“
* for water 60/40 and the inlet temperature = +15 °C