2VV.
Creating innovative solutions for you and your business since 1995.
Table of minimal dimensioning of electrical power cables and circuit breakers used in the ALFA4 EC models.
Parameters of electric
heating/preheating
Circuit breakers for the el.
heating section
Type of power
cord of the
el. heating
section
Regulation
circuit breaker
Type
of power
cord
of regulation
Type of unit
Total
power
(kW)
Voltage
(V)
Current
(A)
Phases
(Pcs)
Current
(A)
Phases
(Pcs)
AHAL4-050HX00E40-XS0...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-050HX00E40-XE1...
3,3
230
14,4
1
CYKY 3Cx2,5
6
1
CYKY 3Cx1,5
AHAL4-050HX00E40-XE2...
6,3
400
9,5
3
CYKY 4Bx2,5
6
1
CYKY 3Cx1,5
AHAL4-050HX00E40-XV2...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XS0...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XE0...
3,3
230
14,4
1
CYKY 3Cx2,5
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XE1...
6,3
400
9,5
3
CYKY 4Bx2,5
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XE2...
9,9
400
14,3
3
CYKY 4Bx2,5
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XE3...
13,5
400
19,5
3
CYKY 4Bx4
6
1
CYKY 3Cx1,5
AHAL4-100HX00E40-XV2...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-200HX00E40-XS0...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-200HX00E40-XE1...
13,5
400
19,5
3
CYKY 4Bx4
6
1
CYKY 3Cx1,5
AHAL4-200HX00E40-XE2...
18
400
26
3
CYKY 4Bx6
6
1
CYKY 3Cx1,5
AHAL4-200HX00E40-XE3...
27
400
39
3
CYKY 4Bx10
6
1
CYKY 3Cx1,5
AHAL4-200HX00E40-XV2...
-
-
-
-
-
6
1
CYKY 3Cx1,5
AHAL4-300HX00E40-XS0...
-
-
-
-
-
6
3
CYKY 5Cx1,5
AHAL4-300HX00E40-XE1...
20
400
29
3
CYKY 4Bx6
6
3
CYKY 5Cx1,5
AHAL4-300HX00E40-XE2...
27
400
39
3
CYKY 4Bx10
6
3
CYKY 5Cx1,5
AHAL4-300HX00E40-XE3...
40
400
58
3
2x CYKY 4Bx6
6
3
CYKY 5Cx1,5
AHAL4-300HX00E40-XV2...
-
-
-
-
-
6
3
CYKY 5Cx1,5
AHAL4-500HX00E40-XS0...
-
-
-
-
-
6
3
CYKY 5Cx1,5
AHAL4-500HX00E40-XV2...
-
-
-
-
-
6
3
CYKY 5Cx1,5
AHAL4-800HX00E40-XS0...
-
-
-
-
-
6
3
CYKY 5Cx1,5
AHAL4-800HX00E40-XV2...
-
-
-
-
-
6
3
CYKY 5Cx1,5