6. INSTALLATION
6.3 CONNECTING THE CONDENSATE
DRAIN
6.3-1 Ceiling installation
6.3-2 Installation on the wall
•
The siphon must have a quality connection and sealed
to the recuperation unit.
•
We recommend to submerge each siphon in water to
check its integrity.
ATTENTION
Improper connection of the siphon may cause flooding and
damage to the heat exchange unit.
The unit is equipped to connect a second con
-
densate drain in places where summer conditions
require it. This second condensate drain must be con
-
nected when the dew point temperature of the inside air
is lower than the outdoor air coming into the building.
These situations may occur, especially in hot summer,
when the high temperature and humidity of the outside
air crosses the low temperature exhaust air inside the
heat recovery core (e.g., + 25 ° c and + 35 ° c between
the inside air and the outside air, with a relative humidity
above 60%). Therefore, we recommend that you install
a second (during summer) condensate drain especially
for chilled air conditioning buildings located in tropical
climates.
The second condensate drain properly connect to the
drain pipe.
Improper connection of the siphon may cause
flooding and damage to the heat exchange unit.
-
Check whether the unit is tilted so the condensate may
run off freely (we suggest 3° tilt, see the figure below).
INSTALLATION OF THE RECOMMENDED TYPE:
Siphon SK-HL138
It can be installed on a wall or concealed.
(not included)
5 °
5 °
0
0
min 100mm
min 100mm
5 °
CONDENSATE DRAIN CONNECTION FOR THE
RIGHTVERSION
(View of the bottom of the unit)
CONDENSATE DRAIN CONNECTION FOR THE
LEFT VERSION
(View of the bottom of the unit)
1) Condensate drain connection for winter period- must
always be connected.
2)Connection of the second condensate drain for the
summer period (the drain is blinded by a blanking plug)-
connected according to the conditions.
1
1
2
2
EHA
EHA
ODA
ODA
SUP
SUP
ETA
ETA