10
5. TECHNICAL PARAMETERS
Air curtains with a water coil for a water temperature gradient of 40/30° C and at an intake air
temperature of +18° C
Type
Air flow
[m3/h]
Heat output
[kW]
Outlet
temperature [°C]
Water flow
[l/s]
Pressure loss
[kPa]
VCF-C-100-W-...
2530
13,47
34
0,2
13,2
VCF-C-150-W-...
3500
19,03
34,3
0,4
14,1
VCF-C-200-W-...
4670
25,71
34,5
0,5
13,3
VCF-C-250-W-...
5260
29,81
35
0,6
16,3
Air curtains with a water coil for a water temperature gradient of 35/25° C and at an intake air
temperature of +18° C
Type
Air flow
[m3/h]
Heat output
[kW]
Outlet
temperature [°C]
Water flow
[l/s]
Pressure loss
[kPa]
VCF-C-100-W-...
2530
9,4
29,2
0,2
8,6
VCF-C-150-W-...
3500
13,3
29,4
0,3
8,2
VCF-C-200-W-...
4670
18
29,6
0,3
8,4
VCF-C-250-W-...
5260
21
30
0,4
9,4
The warm-water temperature coil, made of copper-aluminium alloy, is designed for a
maximum operational water temperature of +100° C and a maximum operating pre-
ssure of 1.6 MPa.