8
5. TECHNICAL PARAMETERS
Air curtains with a water coil for a water temperature gradient of 90º/70° C and at an intake air tempe-
rature of +18° C
Type
Air flow
[m3/h]
Heat output
[kW]
Outlet
temperature [°C]
Water flow
[l/s]
Pressure loss
[kPa]
VCF-B-100-V-...AC
2140
24,77
52,7
0,29
12
VCF-B-150-V-...AC
3100
38,77
55,5
0,46
29,1
VCF-B-200-V-...AC
4280
52,61
54,9
0,62
24,1
VCF-B-250-V-...AC
5140
62,29
54,4
0,74
17,8
VCFI4B-B100-V-...EC
1700
19,14
55,5
0,23
7,75
VCFI4B-B150-V-...EC
2550
29,7
57,1
0,36
21,39
VCFI4B-B200-V-...EC
3400
39,49
57
0,48
18,93
VCFI4B-B250-V-...EC
4250
48,4
56,2
0,59
20,01
VCF-C-100-V-...AC
2800
29,13
49,2
0,35
14,5
VCF-C-150-V-...AC
3900
44,57
52,3
0,53
35,1
VCF-C-200-V-...AC
5070
56,99
51,7
0,68
27
VCF-C-250-V-...AC
5860
62,29
54,4
0,74
17,8
Air curtains with a water coil for a water temperature gradient of 80º/60° C and at an intake air tempe-
rature of +18° C
Type
Air flow
[m3/h]
Heat output
[kW]
Outlet
temperature [°C]
Water flow
[l/s]
Pressure loss
[kPa]
VCF-B-100-V-...AC
2140
20,28
46,4
0,24
8,8
VCF-B-150-V-...AC
3100
31,78
48,8
0,38
20,8
VCF-B-200-V-...AC
4280
43,15
48,3
0,51
17,7
VCF-B-250-V-...AC
5140
51,07
47,8
0,61
13,4
VCFI4B-B100-V-...EC
1700
15,92
48,5
0,19
5,59
VCFI4B-B150-V-...EC
2550
24,92
50,1
0,30
15,89
VCFI4B-B200-V-...EC
3400
33,08
49,9
0,40
13,93
VCFI4B-B250-V-...EC
4250
40,53
49,2
0,49
14,52
VCF-C-100-V-...AC
2800
23,88
43,6
0,28
10,9
VCF-C-150-V-...AC
3900
36,57
46,1
0,43
25,3
VCF-C-200-V-...AC
5070
46,72
45,6
0,55
19,8
VCF-C-250-V-...AC
5860
51,07
47,8
0,61
13,4