6.5-4 Connecting the unit
to a BMS control system
The control of the unit is fitted with a RS-485 inter
-
face as standard. Insert the cable into one of the
connectors on the unit’s electronic board. Connect
the other end to the main control unit. For protocol
details (Modbus-TCP, Modbus-RTU), contact 2VV.
6.6 CONDENSATE DRAIN
CONNECTION
The condensate drain (recuperator section) must
be connected to the drainage piping. The siphon
has built-in antifreeze protection. If a direct evap
-
orator or CO is installed in the unit, a new siphon
(not included) must be connected.
YOU WILL NEED
• 1 siphon
• PVC drainage pipes
• sealing for the drainage piping
h
2
h
1
h
1
Siphon courant
Siphon à boule
Type
h1 [mm]
h2 [mm]
HRFL2-040
HRFL2-070
HRFL2-150
HRFL2-200
130
130
130
130
80
80
80
80
The tank’s neck is located on the side/sides of the
unit.
Attach to it the siphon or to a hose connected to
the drainage.
READ CAREFULLY!
● There should be as much distance as possible
between the supply and control cables.
● Make sure that the cable snaps into the connec
-
tor.
● Be careful not to damage the cable insulation
when fitting the control to a wall or other sur
-
face.
● If the connectors and cables aren’t connected
immediately after installing the unit, protect
them with insulating tape against mechanical
damage or short-circuit.
● The cable connectors must not come into con
-
tact with water or any other liquid.
6. INSTALLATION
- Make sure that the unit is tilted 3° in order to
drain the condensate.
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
EN
RU
CZ
1.
A
(5-6)
LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open)
LF1 ЗАСЛОНКА ВПУСК (выход L-открыт), LF2 - ЗАСЛОНКА ВЫПУСК (выход L-открыт)
LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2.
A
(7-8)
RUN CONTACT (output -NO/NC settable)
RUN контакт (выход - NO/NC устанавливаемый)
RUN KONTACT (výstup -NO/NC nastavitelné)
3.
A
(9-10)
ERROR CONTACT (output NO)
ОШИБКА КОНТАКТА (выход NO)
ERROR KONTACT (výstup NO)
4.
A
(11-12)
PREHEATER WATER PUMP (11 - Lint, 12 - Lout)
ВОДЯНОЙ НАСОС ПРЕДВАРИТЕЛЬНОГО НАГРЕВА (11 - Lint,12 - Lout)
VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5.
A
(13-14)
BOOST (input NO)
BOOST (вход NO)
BOOST (vstup NO)
6.
A
(15-16)
FIRE (input NC)
FIRE -тревога (вход NC)
FIRE (vstup NC)
7.
A
(17-18)
EXTERNAL CONTROL ON/OFF (input NC)
ВНЕШНЕЕ УПРАВЛЕНИЕ ON/OFF (вход NC)
EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8.
A
(18-19)
AQS SENSOR 0-10V (input)
ДАТЧИК КАЧЕСТВА ВОЗДУХА 0-10В (вход)
ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9.
B
(1-2)
WATER PUMP (1 - Lint, 2 - Lout)
ВОДЯНОЙ НАСОС (1 - Lint, 2 - Lout)
VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10.
B
(3-4)
HEAT PUMP CONTROL settable (output - ON/OFF)
УПРАВЛЕНИЕ ТЕПЛОВОГО НАСОСА устанавливаемый (выход - ON/OFF)
ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11.
B
(5-6)
ADIABATIC MODULE (output - ON/OFF)
АДИАБАТИЧЕСКИЙ МОДУЛЬ (выход - ON/OFF)
ADIABATICKÝ MODUL (výstup - ON/OFF)
12.
B
(7-8)
COOL / HEAT settable (CO = NC/NO - DX = output settable)
ОХЛАЖДЕНИЕ /ОБОГРЕВ устанавливаемый (CO = NC/NO - DX = выход устанавливаемый)
CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13.
B
(9-10)
ADIABATIC MODULE ERROR (input NO)
АДИАБАТИЧЕСКИЙ МОДУЛЬ ERROR (вход NO)
ADIABATICKÝ MODUL ERROR (vstup NO)
14.
B
(11-12)
HEAT PUMP DEFROST settable (input NC/NO)
РАЗМОРАЖИВАНИЕ ТЕПЛОВОГО НАСОСА устанавливаемое (вход NC/NO)
ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15.
B
(13-14)
HEAT PUMP ERROR settable (input NC/NO)
ОШИБКА ТЕПЛОВОГО НАСОСА устанавливаемая (вход NC/NO)
CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16.
B
(15-16)
PIR (input NC)
ДАТЧИК ДВИЖЕНИЯ PIR (вход NC)
POHYBOVÉ ČIDLO PIR (vstup NC)
17.
B
(17-18)
CONDENSATE OVERFLOW (input NC)
ДАТЧИК ПЕРЕПОЛНЕНИЯ КОНДЕНСАТА (вход NC)
ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18.
B
(46-47)
EXTERNAL TEMPERATURE SENSOR (external postheater - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (внешний дополнительный нагрев - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19.
B
(44-45)
EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input)
ВНЕШНИЙ ДАТЧИК ТЕМПЕРАТУРЫ (адиабатический модуль / камера рециркуляции - вход)
EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20.
B
(38-39)
EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ПОДОГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21
B
(36-37)
EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM)
ВНЕШНИЙ ДООГРЕВ (выход - вода=0-10В, электрический=PWM)
EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22
B
(34-35)
RECIRCULATION CHAMBER (output 0-10V)
РЕЦИРКИЛИРОВАННАЯ КАМЕРА (выход 0-10В)
RECIRKULAČNÍ KOMORA (výstup 0-10V)
A
B
MODBUS connection