8
9
2VV.
Creating innovative solutions for you and your business since 1995.
ver.3 29-04-20
Characteristics of the C/O reheating
Heating mode
Type
Power* (kW)
Pressure loss
with flow
water [kPa]
Pressure loss
with flow
air [Pa]
Average
connection
Airflow
(m
3
/h)
HRFL2-040
2.51
0.29
80
3/4“
400
HRFL2-070
4.6
0.59
71
3/4“
700
HRFL2-150
9.41
0.69
99
3/4“
1500
HRFL2-200
15.7
1.67
83
3/4“
2000
* Data for 60/40 gradient, inlet temperature = 15°C
Characteristics of the water reheating
Type
Power* (kW)
Pressure loss
with flow
water [kPa]
Pressure loss
with flow
air [Pa]
Average
connection
Airflow
(m
3
/h)
HRFL2-040
1.75
1
10
1/2“
400
HRFL2-070
2.71
3
15
1/2“
700
HRFL2-150
5.92
17
27
1/2“
1500
HRFL2-200
9.22
9
21
1/2“
2000
* Data for 60/40 gradient, inlet temperature = 15°C
Characteristics of the el. preheating
Type
Phases
Tension
Frequency
Input power
(kW)
ΔT
(°C)
HRFL2-040
1
230 V
50/60 Hz
1.35
10
HRFL2-070
1
230 V
50/60 Hz
2.7
10
HRFL2-150
3
400 V
50/60 Hz
5.3
10
HRFL2-200
3
400 V
50/60 Hz
8.4
10
Cooling mode
Type
Power* (kW)
Pressure loss
with flow
water [kPa]
Pressure loss
with flow
air [Pa]
Average
connection
Airflow
(m
3
/h)
HRFL2-040
1.94
2.65
91
3/4“
400
HRFL2-070
3.68
5.4
80
3/4“
700
HRFL2-150
7.34
6.57
112
3/4“
1500
HRFL2-200
12.62
15.79
94
3/4“
2000
* Data for 7/12 gradient, inlet temperature = 25°C
Characteristics of the direct DX evaporator
Type
Airflow
(m
3
/h)
Power*
(kW)
Temperature
behind the direct
evaporator
(°C)
RH (%)
Fluid pressure
loss
(kPa)
Air pres-
sure loss
(Pa)
Connection
(gas)
Connection
(fluid)
HRFL2-040
400
2.54
10
92
11
79
1/2“
1/2“
HRFL2-070
700
4.65
10
92
41
69
1/2“
5/8“
HRFL2-150
1500
9.94
10
92
12
97
1/2“
7/8“
HRFL2-200
2000
16.15
10
92
28
91
3/4“
7/8“
* Data for 27°C inlet temperature, Cooling R410A.
Evaporation temperature 5°C.