MENU - HW SETTING
Motor 1
In the quantity of the “number of
motors” menu, select the value “1”
Motor 10
..........
GND
GND
Ad 1)
Ad 2)
Ad 3)
Ad 4)
Door contact (NO/NC)
External control contact
(NO/NC)
Error contact (NO/NC)
Ad 1)
- Activation/settings of outer temperature sensor. Available selections:
None
- sensor not connected/inactive
EXT-1 (45,46)
- sensor connected (must be on connectors 45 and 46)
BMS
- temperature sensor active and used from master system
Ad 2) - Setting the behaviour of external contact input. Available selections:
None
- inactive
External control
- External activation/deactivation of device
Night reduction
- Activation/deactivation of night dimming
(settings described later in this guide)
Ad 3) - Thermostat (NO/NC)
Ad 4) - Number of connected EC motors on regulator: 0-10pcs
Don't forget to connect the speed outputs of the motors to the appropriate connectors
on the panel of the regulator, per the following schematic:
If the situation should occur that it is not required to check the speed output of the motors,
this function can be blocked:
And join the 1+2 connectors per the schematic below.
In this MENU you can set the detailed behaviour of the in-
dividual regulator inputs and outputs
Servicing menu
MENU - MODE
Use code 1616 to access the servicing MENU
1616
Select the
MENU after
scrolling to the
middle of the
page and click-
ing to enter
If you set the function AUTO or MANUAL, certain items can
be enabled/disabled in the servicing MENU
Enter menu
Enter selected menu
Delete/go back
Select MANUAL/AUTOMATIC heating
mode
Activation/deactivation of automatic motor
rotation control by temperature
7. CONTROL