Manual WS.502 v1.5
2-Wire Energy Monitor
33
RESET SUMMARIZED:
Pressing keys while running:
1.
Key 1: Upgrading Javascript and CSS.
2.
Key 2: Upgrading firmware Web server WS502
Pressing keys during startup voltage:
3.
Toets 1: clear full database, IP address reset,
login and password
4.
Key 2: Reset IP address and password.
FAULTY JAVASCRIPT/STYLE: TEST 1+TEST 2
If you discover errors on the website, or there is no
key that responds, even after 'refresh page', an error
may have crept in when loading the script/style. There
are a few ways to download the javascript and
possibly the firmware again:
1.
Via the Login page
2.
Manually using the push buttons on the web
server
3.
Remote via an http statement
VIA THE LOGIN PAGE
With the "SCRIPT REPAIR" button on the login page,
you can reload javascript from another location.
MANUALLY USING THE PUSH BUTTONS ON THE WEB
SERVER
Re-download the java script from the 2-WIREserver by
pressing key 1 (left, shortest against the power
connector) and keep pressing until the left LED is
continuous. Only then release key. Now the LED
should stay on for 15 to 20 seconds and then go out
again.
Key 2
:If this is okay, then you do the same thing with
the right push button (key 2): keep pressing until the
flash stops and both LEDs are constantly burning, then
release key.
Now the LEDs also have to light 15 to 20 sec and then
the right LED starts flashing very quickly. After that,
the LED will burn continuously for about 3 seconds
and then go out. Everything okay !!!
When these things happen as described, try refresh
page again and log in.
REMOTE VIA AN HTTP STATEMENT
If you only have remote access to the web server, you
can use the following http instructions TO remotely
execute KEY1 (upgrade css/javascript) and KEY 2
(memo2 firmware upgrade).
Method:
Step 1:Ask for an access: enter your own
IP address
+
login
+
password
to get an XP key
ask XP key:
http://
192.168.0.123:8080
/
adminIP
?
XP
2015
&
antw: |4|13|
5|4
|0|
54 = XP-key
Step 2: Order upgrade css (KEY1):
req upgr FW CSS & script:
http://
192.168.0.123:8080
/
adminIP
?
XP
54
&DLFwStyleScript&
antw na ca 10sec: _30/06
9:26_|0|18|84|20.6.28.1|☑|0 = FW css
& script FW 20.6.28.1
Step 3: Order firmware upgrade (KEY2):
req upgrading FW server:
http://192.168.0.123:8080/adminIP?XP54&DL
FwWeb&
antw na ca 10sec: _30/06
9:26_|0|19|84|20.6.29.4|☑| START
UPGRADING|0 (FW 20.6.29.4)
Afterwards in toolbar get rid of instructions, reload
page and log in normally!
CLEAR FULL DATABASE, RESET IP ADDRESS AND
PASSWORD: KEY 1
Key 1 (shortest against power connector):
Procedure: Turn off
voltage of the WS502, wait 5
seconds, hold down key 1, turn on voltage, and keep
pressing until the LED starts flashing. Keep pressing
for another 3 seconds until the LED stops blinking and
then release the key.