Step
1/2" (13 mm)
Mastic Strip
Clean and Lubricate
Attach Ground
Lead to Elbow
Grounding Tab
Step
Cold Shrink Tubing
Counter-Clockwise
7.5
7.6
7.5 Remove white liners from remaining mastic strip and
apply around base of elbow,
1
⁄
2
" (13 mm) from step as
shown. Apply 1 layer of vinyl tape over mastic.
7.6 Align Cold Shrink rubber tube (not core) with step of
elbow. Remove core by pulling and unwinding the
core counter-clockwise.
• Attach 14 AWG ground lead (from ground braid
assembly) to the elbow grounding eye. Connect
ground braid to system ground. (For jacketed
concentric neutral cable, attach a neutral strand to
grounding eye, and connect remaining neutral bundle to
system ground.)
9
78-8124-4544-9-B
Connector
5
/
8
" Diameter
3
/
4
" Diameter
Conductor Size
4 AWG through 2/0 Stranded
3/0 AWG through 250 kcmil Stranded
Tool
Y34
Y35 OR Y39
MD6
Y34
Y35 OR Y39
MD6
A243
U243
UBG
W243
WBG
U247
U247
U467
W247
Burndy
Die
A25AR
U25ART
U687
BG
W687
A27AR
U27ART
Nose
Thomas
Tool
UT-3
UT-5
UT-15
UT-5
UT-15
& Betts
Die
5
/
8
"
TV
54 H
TV
66
Kearney
Tool
0
H-1, H-2
0
H-1, H-2
Die
5
/
8
"
Nose
9
/
16
"
9
/
16
"
572
737
747
737
747
Alcoa
Tool
12A
12A
Die
B24 EA
B39 EA
Anderson Tool
VC-5, VC-6
VC-5, VC-6
EEI—Reference
8A
10A
Table 2.
Crimp Chart.
Summary of Contents for 5811 Series
Page 11: ...11 78 8124 4544 9 B ...