Kit No.
Cable O.D.
Conductor Size
Sheath Opening
90-B1
Feeder Cable
Split Bolt
1/2" to 13/16"
1/0 AWG (max.)
3" maximum
90-B1
Branch Cable
Crimped
3/8" (max.)
2/0 AWG (max.)
3" maximum
Scotchcast
™
Power Cable Tap
Splice Kit 90-B1
Instructions
1.0 Applications
Designed for use in weather-exposed or direct-burial locations. For making tap or branch splices on unshielded,
synthetic insulated cables rated up to a maximum of 1000 volts. These kits will accommodate the following
connectors and conductor sizes:
D
C
B
A
A
2.0 Kit Contents
Mold Body .................................................... A
Pouring Spout ............................................... B
Scotch
®
Electrical Tape 23 ............................ C
3M
™
Scotchcast
™
Resin 4 ............................. D
3.0 Prepare Cable
3.1
Thoroughly scrape all wax and dirt 3" back from
each cable end. Prepare cable ends exactly as shown
in Figure 1.
Figure 1
1 1/4" (max)
1 1/4" (max)
CAUTION
Working around energized electrical systems may cause serious
injury or death. Installation should be performed by personnel
familiar with good safety practice in handling electrical equipment.
De-energize and ground all electrical systems before installing
product.