13
78-81
41-4631-8
-
A
rubber
mastic
2.6
Install Jacket for CN Splices
Note:
Jacketing is not optional.
2.6.1 Apply one roll of rubber mastic over each mastic seal (tacky side toward cable).Tear off the end of the
rubber mastic.
For CN to CN Splices
torn-off end
Note:
If grounding splice, leave sufficient neutral wire length to extend neutral wires through the inline
compression connectors for connection to the ground wire per Wisconsin Electric specifications.
2.5.2 Connect the neutral wires using inline compression connectors. The neutral wires should pass through the
connector, making an overlap crimp. Trim excess neutral wire on both sides for a non-grounded splice or
on the spice body side only for a grounded splice. All connections must be made over the neutral pad.
After all of the neutral wires are connected. Wrap a mastic strip over the end of the cable jacket and the
previously applied mastic on both sides of the splice.
Neutral connection without splice grounding
Neutral connection for a grounding splice
Neutral wire ends
Mastic
Neutral wire ends
Grounding wires