5
78-8
141-4631
-
8
-
A
2.1
Prepare Cables
2.1.1 Prepare cables according to standard procedures. Refer to template provided or illustration below for
proper dimensions.
Additional distance is required on one cable to provide extra neutral wire length
for connecting the neutrals.
Jacketed Concentric Neutral (JCN)
Concentric Neutral (CN)
extra neutral
wire length
13" (330 mm)
8 1/2" (216 mm)
Note:
Cables must be within the Insulation O.D. Range of the splice kit and the connector must meet
the dimensional requirements shown on the front page.
13" (330 mm)
8 1/2" (216 mm)
4 1/2"
(114 mm)
4 1/2"
(114 mm)