3
78-8124-5866-5-E
3M
™
Cold Shrink QT-lll Silicone Rubber Three Core Inverted Skirted Termination
with High-K Stress Relief
2.0 Prepare Cable
2.1
Determine cable jacket removal length required for correct phase spacing and bolted terminal lug connections
([A] + [B] Figure 1; based on the longest phase to be connected). Allow for dimension [C] as needed.
NOTE: Individual phase length and separation dimensions vary according to specific installation and equipment design
requirements. They must, therefore, be determined by the installer and must conform to accepted engineering
practices. Max phase length = 4 ft (121,9 cm) + termination length (from Figure 18, page 14).
2.2 Remove cable jacket, armor, bedding (inner sheath) and core fillers according to Figure 1 dimensions. Secure
copper tape shield ends with temporary bands of vinyl tape (Figure 1).
NOTE: DO NOT DISCARD LEFTOVER JACKET MATERIAL.
Temporary Bands
of Vinyl Tape
Ground Wire
Copper Tape Shield
2” (51 mm)
Armor
[A]
Jacket
Removal
Length
[A] + [B]
[B]
[C]
Ground Wire
Figure 1