78-8124-5866-5-E
3M
™
Cold Shrink QT-lll Silicone Rubber Three Core Inverted Skirted Termination
with High-K Stress Relief
1.0 Kit Contents
(1) Cold Shrink Silicone Rubber Breakout Boot Assembly
(1) Cold Shrink Silicone Rubber Jacket Seal Assembly
(3) Silicone Rubber Phase Rejacketing Sleeve Assemblies
(3) Cold Shrink Silicone Rubber Tubular Termination Assemblies
(3) Cold Shrink Silicone Rubber Skirt Assemblies
(1) Tinned Copper Ground Braid Assembly
(3) Constant-Force Springs (Small)
(1) Constant-Force Spring (Large)
(8) Strips Scotch
®
Mastic Strip 2230 (Two per termination & two per breakout boot bag)
(1) Roll Scotch
®
Super 33+
™
Vinyl Electrical Tape - 3/4"
(1) Roll Scotch
®
Vinyl Electrical Tape Super 88 - 1-1/2"
(1) Roll Scotch
®
Electrical Shielding Tape
(3) 3M EMI Copper Foil Shielding Tape 1181 Strips - 1/2" x 10"
(1) 3M Cable Cleaning Preparation Kit CC-2
(1) Instruction Sheet
NOTE: Do Not use knives to open plastic bags.
Kit Selection Table
Note: Final Determining Factor is Cable Insulation Diameter.
Kit Number
Insulation
Range
Min - Max
Inch (mm)
Max
Cable
O. D.
Inch (mm)
Conductor Size Range (AWG and kcmil)
5 kV
8 kV
15 kV
25 kV
100%
133%
100%
133%
100%
133%
100%
133%
7693-S-4-INV-3G
0.92 - 1.18
(23,4 - 30,0)
3.90
(99,1)
400 -
500
400 -
500
400 -
500
400 -
500
250 -
350
4/0 -
350
2/0 -
250
1 - 4/0
7695-S-4-INV-3G
1.18 - 1.52
(30,0 - 38,6)
4.50
(114,3)
700 -
1000
700 -
1000
700 -
1000
700 -
1000
500 -
750
500 -
750
350 -
500
250 -
500
7620-S-2-INV-3G
0.33 - 0.50
(8,4 - 12,7)
2.20
(55,9)
8 - 2
6 - 4
6 - 4
6 - 4
-
-
-
-
7621-S-2-INV-3G
0.50 - 0.70
(12,7 - 17,8)
2.80
(71,1)
1 - 3/0
2 - 2/0
2 - 2/0
2 - 2/0
-
-
-
-
7622-S-2-INV-3G
0.70 - 0.92
(17,8 - 23,4)
3.30
(83,8)
4/0 -
350
3/0 -
350
3/0 -
350
3/0 -
350
1/0 -
4/0
2 - 3/0
-
-