FL485
Surge Protection Devices For
Twisted-Pairs System
Quick Installation Guide
3onedata Co., Ltd.
Address: 3/B, Zone 1, Baiwangxin High Technology
Industrial Park, Xili, Nanshan District, Shenzhen
Website: www.3onedata.com
Tel: +86 0755-26702688
Fax: +86 0755-26703485
【
Package Checklist
】
Please check whether the package and accessories are intact
while using the device for the first time.
1 Surge protection device
2 Quick installation guide
3 Certification
4 Warranty card
If any of these items are damaged or lost, please contact our
company or dealers, we will solve it ASAP.
【
Product Overview
】
The product is RS-485 surge protection device. Model is:
FL485 (1 RS-485 input +1 RS-485 output).
【
Mounting Dimension
】
Unit: mm
Note before mounting:
Dont place or install the device in area near water or
moist, keep the relative humidity of the device
surrounding between 5%~95% without condensation.
Before power on, first confirm the supported power
supply specification to avoid over-voltage damaging the
device.
The device surface temperature is high after running;
please dont directly contact to avoid scalding.
【
The Method of Maintenance
】
This product is connected in series. The surge protection
device is installed in the front end of the protected
equipment. The “IN” of the surge protection device is the
input side, and the “OUT” is the output side. That is, the
external signal cable is connected to the “IN (Line)” end
of the surge protection device, The protected device is
connected to the “OUT (Equip)” end of the surge
protection device;
The length of the connection line between the protected
equipment and the surge protection device should not
exceed 0.5 meters, it is better that the surge protection
device is closer to the protected equipment;
The PE line of the surge protection device is connected
to the equipotential bonding terminal of the protected
device first, and then reliably connected with the
grounding network of the lightning protection system.
The connection line is required to be short, thick and
straight;
The components in the surge protection device are
strictly tested. Normally, no special maintenance is
required. The surge protection device should be
regularly tested during use. Remove the surge protection
device during fault detection. The resistance between
the input and output should be
≤
11
Ω
, and the
resistance between the core line and ground should be
≥
10
ΜΩ
.If there is a fault, it should be repaired or
replaced in time to ensure the safety of the equipment.
【
Specification
】
Specifications
Nominal operating voltage / Un
5V
Maximum continuous operating
voltage / Uc
6V
Nominal discharge current /
In(8/20us)
500A(Line-line),
3000A(Line-ground)
Maximum discharge current /
Imax(8/20us)
1000A(Line-line),
5000A(Line-ground)
Voltage protection level /
Up(1.2/50us)
<30V(Line-line),
<600V(Line-ground)
Impulse withstand voltage
(10/700us)
6000V(Line-line,
Line-ground)
Insertion loss
≤
0.5dB
Number of protection lines
2 lines
Transmission rate
0-10Mbps
Interface type
3Pin 5.08 terminal
blocks
Degree of protection
IP20
Response time
≤
10ns
Working temperature
-20
℃
~+60
℃
Dimensions
73
*
25
*
25 (±1) mm
Net Weight / Gross weight
49 / 67 (±5) g