background image

 

 

 

FL485 

Surge Protection Devices For 

Twisted-Pairs System 

Quick Installation Guide 

 

3onedata Co., Ltd. 

Address: 3/B, Zone 1, Baiwangxin High Technology 
Industrial Park, Xili, Nanshan District, Shenzhen 
Website:  www.3onedata.com 
Tel:       +86 0755-26702688 
Fax:      +86 0755-26703485 

 
 

Package Checklist

 

Please check whether the package and accessories are intact 
while using the device for the first time. 

1  Surge protection device 

2  Quick installation guide 

3  Certification 

4  Warranty card 

If any of these items are damaged or lost, please contact our 
company or dealers, we will solve it ASAP. 

Product Overview

 

The product is RS-485  surge protection device.  Model  is: 
FL485 (1 RS-485 input +1 RS-485 output). 

Mounting Dimension

 

Unit: mm 

 

Note before mounting: 

 

Dont place or install the device in area near water or 
moist, keep the relative humidity of the device 
surrounding between 5%~95% without condensation. 

 

Before power on, first confirm the supported power 
supply specification to avoid over-voltage damaging the 
device. 

 

The device surface temperature is high after running; 
please dont directly contact to avoid scalding.  

The Method of Maintenance

 

  This product is connected in series. The surge protection 

device is installed in the front end of the protected 
equipment. The “IN” of the surge protection device is the 
input side, and the “OUT” is the output side. That is, the 
external signal cable is connected to the “IN (Line)” end 
of the surge protection device, The protected device is 
connected to the  “OUT (Equip)”  end of the surge 
protection device; 

  The length of the connection line between the protected 

equipment and the surge protection device should not 
exceed 0.5 meters, it is better that the surge protection 
device is closer to the protected equipment; 

  The PE line of the surge protection device is connected 

to the equipotential bonding terminal of the protected 
device first, and then reliably connected with the 
grounding network of the lightning protection system. 
The connection line is required to be short, thick and 
straight; 

  The components in the surge protection device are 

strictly tested. Normally, no special maintenance is 
required. The surge protection device should be 
regularly tested during use. Remove the surge protection 
device during fault detection. The resistance  between 
the input and output should be 

11

Ω

, and the 

resistance between the core line and ground should be 

10

ΜΩ

.If there is a fault, it should be repaired or 

replaced in time to ensure the safety of the equipment. 

Specification

 

Specifications 

 

Nominal operating voltage / Un 

5V 

Maximum continuous operating 
voltage / Uc 

6V 

Nominal discharge current / 
In(8/20us) 

500A(Line-line), 
3000A(Line-ground) 

Maximum discharge current / 
Imax(8/20us) 

1000A(Line-line), 
5000A(Line-ground) 

Voltage protection level / 
Up(1.2/50us) 

<30V(Line-line), 
<600V(Line-ground) 

Impulse withstand voltage 
(10/700us) 

6000V(Line-line, 
Line-ground) 

Insertion loss 

0.5dB 

Number of protection lines 

2 lines 

Transmission rate 

0-10Mbps 

Interface type 

3Pin 5.08 terminal 
blocks 

Degree of protection 

IP20 

Response time 

10ns 

Working temperature 

-20

~+60

 

Dimensions 

73

*

25

*

25 (±1) mm 

Net Weight / Gross weight 

49 / 67 (±5) g 

 

Summary of Contents for FL485

Page 1: ...excellent lightning protection performance built in multi level surge protection large surge capacity high speed response nanosecond level low residual voltage level chip level protection for the protected equipment small size easy wiring installation convenience The internal equipotential design of the lightning arrester can effectively prevent equipment damage caused by the instantaneous increas...

Page 2: ...es induced in the line and protects the back end equipment from lightning and industrial surge This product is made of aluminum alloy shielded metal casing has good sealing performance and has dustproof and anti corrosion function It is connected in series and installed between the protected equipment and the outer line Dimension Unit mm Specification Nominal operating voltage Un 5V Maximum contin...

Page 3: ...s 2 lines Transmission rate 0 10Mbps Interface type 3Pin 5 08 terminal blocks Degree of protection IP20 Response time 10ns Working temperature 20 60 Dimensions 73 25 25 1 mm Net Weight Gross weight 49 67 5 g Certification CE FCC RoHS Warranty 1 year ...

Page 4: ... Road Nanshan District Shenzhen 518108 China TEL 86 755 26702668 ext 835 FAX 86 755 26703485 E mail ics 3onedata com Website www 3onedata com Please scan our QR code for more details Product pictures and technical data in this datasheet are only for reference Updates are subject to change without prior notice The final interpretation right is reserved by 3onedata ...

Page 5: ... connected to the OUT Equip end of the surge protection device The length of the connection line between the protected equipment and the surge protection device should not exceed 0 5 meters it is better that the surge protection device is closer to the protected equipment The PE line of the surge protection device is connected to the equipotential bonding terminal of the protected device first and...