background image

The model II of this series provides 5-Pin 
5.08mm pitch terminal blocks. The serial 
port is isolated and its pin definitions are 

as follows: 

PIN 

5. 

RS-485 

D+ 

D- 

GND 

— 

— 

RS-422 

T+ 

T- 

GND 

R+ 

R- 

Checking LED Indicator

 

The device provides LED indicators to monitor the device 
working status with a comprehensive simplified 
troubleshooting; the function of each LED is described in the 
table as below: 

LED 

Indicate 

Description 

PWR 

ON 

PWR is connected and running 
normally 

OFF 

PWR is disconnected and running 
abnormally 

RUN 

Blinking 

System runs normally 

OFF 

The system is not running or running 
abnormally 

ON 

System is running abnormally 

LINK 
(1-2) 

ON 

Copper port has established an 
active network connection. 

Blinking 

Copper port is in a network activity 
state. 

OFF 

Copper port has not established an 
active network connection. 

TX(1-4) 

OFF 

No data or abnormal data is being 

transmitted through serial port. 

Blinking 

Serial port is transmitting data. 

RX(1-4) 

OFF 

Serial port is not receiving data or 
receiving data abnormally 

Blinking 

Serial port is receiving data. 

Logging in to WEB Interface

 

This device supports WEB management and configuration. 
Computer can access the device via Ethernet interface. The 
way of logging in to device’s configuration interface via IE 
browser is shown as below: 
Step 1 

Configure the IP addresses of computer and the 
device to the same network segment(The network 
segment of Network Port  1 is 1, and the network 
segment of network port 2 is 8), and the network 
between them can be mutually accessed. 

Step 2 

Enter device’s IP address in the address bar of the 
computer browser. 

      Network Port 1: 

 

Network Port 2: 

 

Step 3 

Enter device’s username and password in the login 
window as shown below. 

 

Step 4 

Click “OK” button to login to the WEB interface of 
the device. 

Notes: 

 

The default IP address of the device network port 1 is 
“192.168.1.254”, port 2 is “192.168.8.254”. 

 

The default username and password of the device

 

are 

“admin”. 

 

If the username or password is lost, user can restore it to 
factory settings via device DIP switch or management 
software; all modified configurations will be cleared 
after restoring to factory settings, so please backup 
configuration file in advance. 

 

Please refer to user manual for specific configuration 
method of logging in to WEB interface and other 
configurations about network management function. 

Specification

 

Panel 

 

100M Copper Port

 

10/100Base-T(X)  self-adapting RJ45 
port

 

Serial Port

 

  3IN1 RJ45 interface or RS-485/422 
terminal block with isolation

 

Indicator 

Power indicator, Running indicator, 
Copper port connection indicator, 
Serial port transmission and 
receiving data indicator 

Power supply

 

 

Input power supply

 

12

48VDC

 

Access terminal 
block 

3-pin 5.08mm pitch terminal blocks

 

Power 
consumption 

 

Model I

 

No-load: 2.16W@12VDC 
Full-load: 3.00W@12VDC

 

Model II

 

No-load: 2.94W@12VDC 
Full-load: 2.94W@12VDC 

Working 
environment 

 

Working 
temperature 

-40~75

 

Working humidity 

5%

95% (no condensation) 

Protection grade 

IP30(metal) 

 