DIN-Rail Mounting

 

The product adopts 35mm standard DIN-Rail mounting which 
is suitable for most industrial scenes, mounting steps as 
follows: 

 

Step 1 

Check if the DIN-Rail mounting kit is installed firmly. 

Step 2 

Insert the bottom of DIN-Rail mounting kit (one side 
with spring support) into DIN-Rail, and then insert 
the top into DIN-Rail. 

Tips: 
Insert a little to the bottom, lift upward and then insert 
to the top. 

Step 3 

Check and confirm the product is firmly installed on 
DIN-Rail, then mounting ends. 

Disassembling DIN-Rail

 

Step 1 

Power off device. 

Step 2 

After lifting the device upward slightly, first shift out 
the top of DIN-Rail mounting kit, and then shift out 
the bottom of DIN-Rail, disassembling ends. 

Notice: 

 

Don't place or install the device in area near water or 
moist, keep the relative humidity of the device 
surrounding between 5%~95% without condensation. 

 

Before power on, first confirm the supported power 
supply specification to avoid over-voltage damaging the 
device. 

 

The device surface temperature is high after running; 
please don't directly contact to avoid scalding. 

Power Supply Connection

 

 

12~48VDC power supply 

Model I, VI, VIII devices of this series support 
DC power input, and provide 3-pin terminals 
with a spacing of 7.62 mm. The power supply 
has non-polarity function. Voltage range: 

12~48VDC. The pin definitions of power supply are shown as 
follows: 

PIN 

Definition 

V+ 

FG 

V- 

 

48VDC power supply 

Model III, IV, V devices of this series support 
DC power input, and provide 3-pin terminals 
with a spacing of 7.62 mm. The power 
supply has anti-reverse connection function. 

Support 48V PoE, power range: 48VDC (44~55VDC). The pin 
definitions of power supply are shown as follows: 

PIN 

Definition 

V+ 

FG 

V- 

 

AC power supply 

Model II, VII, IX devices of this series support 
AC power input, and provide 3-pin terminals 
with a spacing of 7.62 mm. Power supply 
value range is: 220VAC (100~240VAC). The 

pin definitions of power supply are shown as follows: 

PIN 

Definition 

FG 

Notice: 

 

Power ON operation: First insert the power supply 
terminal block into the device power supply interface, 
and then plug the power supply plug contact and power 
on. 

 

Power OFF operation: First, remove the power plug, 
and then remove the wiring section of terminal block. 
Please pay attention to the above operation sequence. 

DIP Switch Settings

 

This series provide 4-pin DIP switch for function 
setting, where "ON" is the enabled  end. DIP 
switches definition as follows: 

DIP  Definition 

Operation 

Jumbo frame  Set the DIP to ON to enable jumbo 

frame function 

Flow Control 

Set the DIP to ON to enable flow 
control function 

One-key 
VLAN 

Set the DIP to ON to enable VLAN 
function. 

  Model I-Model III: copper port 

1 is interconnected with other 
interfaces, and other ports 
except copper port 1 are 
isolated from each other. 

  Model IV- Model IX: fiber port 

(5 ports

port is interconnected 

with other interfaces, and 
other ports except fiber ports 
are isolated from each other. 

Port 100M 

Set the DIP to ON, port rate would 
be forced to be in 100M 

[Checking LED Indicator] 

The device provides LED indicators to monitor the device 
working status with a comprehensive simplified 
troubleshooting; the detailed status of each LED is described 
in the table as below: 

LED 

Indicate  Description 

PWR 

ON 

PWR is connected and 