3-2
Installation
3-2-1
Pipe Mounting
3-2-2
Wall-Mounting
3-3
Pneumatic and Electrical Installation
3-3-1
Pneumatic Installation
The I/P Converter requires a clean and dry air supply. Provide a system able to deliver such
an air supply.
①
The I/P Converter can be ordered with either Rc1/4 or 1/4NPT couplings. Ensure you use
the correct couplings to match those on I/P Converter.
②
Connect the piping using the appropriate procedure depending upon whether a reducing
valve (Mini-Set XR100) is fitted or not.
If a reducing valve is not fitted, connect to the SUPPLY inlet on the I/P Converter.
If a reducing valve (Mini-Set XR100) is fitted, connect to the “P1” coupling on the Mini-Set
unit.
③
Ensure you fully purge the piping before connection to prevent any particles of dirt or
foreign material from entering the system.
④
Adjust the supply pressure to deliver a 140kPa (1.4kgf/cm
2
) air supply. If using a Mini-Set,
turn the adjustment knob on the Mini-Set to set the pressure to 140kPa (1.4kgf/cm
2
).
3-2