6.
Troubleshooting
Refer to the table below in the event of problems with the I/P Converter .
If the action described below does not restore the transducer to normal operation, replace the I/P
Converter with a spare and contact us.
Symptom
Cause
Action
I/P Converter
does not operate
when an input
signal is applied.
Fixed orifice is blocked.
Clean or replace fixed
orifice.
I/P Converter
is set to manual
operation.
Change to Auto (A)
operation.
Polarity of input signal wiring is
reversed.
Check wiring and
connections.
No air supply
Supply 140kPa
(1.4kgf/cm[2])
Pilot relay is faulty.
Inspect and/or replace
pilot relay.
Output is
unstable.
Large fluctuation in air supply
pressure
Ensure air supply
pressure is constant.
The pressure leakage (volume) on
the output circuit side is fluctuating.
Check for pressure leaks.
Pilot relay is faulty.
Inspect and/or replace
pilot relay.
Large output
error
Zero and span settings are out of
adjustment.
Re-adjust zero and span
settings.
Large fluctuation in ambient
temperature
Fit thermal insulation or
similar.
Pressure leak in output circuit
Fix pressure leak.