Field Remote Control Module - FIM-RC
D
e
te
c
t
-
L
o
c
a
te
-
Is
o
la
te
Hacousto Holland bv - Industrieweg 87 - Berkel en
Rodenrijs - Netherlands -
NOTE
FIM-RC IS NOT EQUIPPED WITH ISOLATOR FUNCTION
DC Power supply (from LDB)
19 - 30 VDC, nominal 30 VDC
Volume override (from VACIE)
20kHz fade-in: 0,3s / fade-out: 1,s
Default threshold: 5Vac
Adjustable Threshold range: 3 - 17Vac
DC Power consumption
idle current
100
μ
A continuous
max. power consumption
20mW
LOOP connection
DC
30V
AC Voltage
100Vrms
AC Frequency range
40Hz - 20kHz (-3dB)
Wiring Loop
2-wire. Max. 2,5mm2 / Max. Loop length: 1000m
Pilots-tone
20kHz
T-Branch output
2x relay contact
2x 2-pol change-over contact
max. AC switching load
2000W (230VAC/8A)
Grounding
optional earth loop through third connection pin
Mechanical
Housing
PP plastic with transparent cover
Dimensions (WxHxD)
IP 21 housing, 110 x 130 x 55 mm (Basic)
IP 33 extension included. 110 x 180 x 55 mm (Optional)
Ordering information. Part No.
FIM-RC
1x IP21 housing with transparent cover and PCB
1 x release tool / 1 x compression gland for speaker mounting
Certification and Approvals
Complies with
n.a.
European patent
n.a.
F
IM-R
C
Q
IG
-
V0
2
R
0
1
Quickguide
LOOP
DRIVE
The FIM-RC acts as a remote contact interface that can activate or
deactivate a third party instrument or equipment that needs to be triggered
during a live-broadcast of an evacuation event. The FIM-RC sits in the LOOP
and receives the broadcast audio message. As soon as the broadcast audio
message contains a 20kHz pilote-tone, the on-board relays of the FIM-RC
will change state into ‘override’ mode. The state change is latched as long
as the pilote-tone is received.
Depending on the function of the third party instrument or equipment, the
FIM-RC offers two potential free NC and a NO switching contacts.
The Loopdrive - Fault Isolator Module (FIM) is the successor in our range of
loudspeaker loop-isolator devices that are using our patent technology to
deliver a higher level of security of evacuation loudspeaker lines that are
installed according to the return-loop principle.
16