November 2022
6022221B - Direct Drive HVLS Fan UM
17
Installation Considerations
INSTALLATION CONSIDERATIONS
Figure 1
ROOF SLOPE
The chart below does not account for any possible obstructions below the mounting positions. All
fans must still maintain 3’ between blades and typical obstructions.
DIRECT DRIVE FAN
Roof Slope*
0
2/12
3/12
4/12
Hanging
Weight
(LB)
Maximum
Torque
(Ft. Lb.)
Roof Angle*
0
9.5°
14.0°
18.4°
Blade
Length (in)
Fan Diameter
Extension requirement from mounting point (FT)
8
0
1
1
2
179.1
300
21.16
10
0
1
2
2
187.4
300
33.16
12
0
1
2
2
195.8
300
45.16
14
0
2
2
3
230.0
300
57.16
16
0
2
2
3
238.7
300
69.16
18
0
2
3
3
247.0
300
81.16
20
0
2
3
4
255.4
300
93.16
24
0
2
3
4
272.1
300
117.16