37
Electrical Schematics
MULTI-FAN WIRING DETAILS — OPTIONAL
Figure 25
LAST FAN IN
COMMUNICATIONS CHAIN
FAN 1
BELDEN 8723 OR EQUIV.
COMMUNICATION CABLE
(SUPPLIED BY OTHERS)
(CONDUIT BY OTHERS)
D+
D-
SC
GREEN
RED
BLACK
D+
D-
GREEN
RED
BLACK
SC
TYPICAL MULTI FAN
DAISY CHAIN
EN
COM
FA
TO BUILDING FIRE ALARM SYSTEM
N.C. DRY CONTACTS
(SUPPLIED BY OTHERS)
FAN N+1
RED
BLACK
GREEN
GREEN
RED
BLACK
MULTI FAN HMI
NETWORK FIRE CONTROL PANEL (6020547)
LOCATE AS CLOSE TO BUILDING FIRE ENCLOSURE
AS POSSIBLE
SUPPLY VOLTAGE 115VAC
(SUPPLIED BY ENTREMATIC AS AN OPTION
FG
VDC
GND
D+
D-
WHITE
GREEN
RED
BLACK
FAN N
DATA0+
DATA0-
+Vs
GND
DATA1+
DATA1-
1
10
11
20
RS485 REPEATER (6019135)
(SUPPLIED BY ENTREMATIC)
(AS AN OPTION)
RED
BLACK
GREEN
WHITE
FOR TOTAL CABLE RUN LONGER THAN 3000 FT
A RS485 REPEATER MAY BE REQUIRED
(INSTALL IN THE VFD ENCLOSURE THAT IS NEAREST THE MIDDLE OF
WHOLE DAISY CHAIN)
(LENGTH OF CABLE IS BASED ON BELDEN 8723 USING OTHER CABLE MAY
REDUCE THE LENGTH BEFORE A REPEATER IS NECESSARY)
WHITE
RED
BLACK
VFD ENCLOSURE
z
The recommended cable for multi-fan and iFAN is Belden 8723
Download
Download
this drawing
this drawing
to view this drawing.