10
storage capacities
taBle 2
moDEL
U. S. GALLoNS LITERS
bTH 300
130
492
bTH 400
130
492
bTH 500
130
492
figure 6
These designs comply with the current edition of the American National Standard for Gas Water Heaters, Volume iii, ANSi Z21.10.3
/ CSA 4.3 as an automatic circulating tank water heater, and automatic storage water heaters.
rough in dimensions
gas line connection siZe
taBle 1
moDEL
SERIES NATURAL GAS
PRoPANE GAS
bTH 300
100/101
1 1/4” NPT
1 1/4” NPT
bTH 400
100/101
1 1/4” NPT
1 1/4” NPT
† bTH 500
100/101
1 1/4” NPT
1 1/4” NPT
† This table shows connections sizes only. BTH 500 natural gas models require
a 1 1/2” minimum supply gas line - see Table 5 on page 13 for minimum required
supply gas line sizes. Depending on the installed equivalent length, and/or
the number of appliances connected, the supply gas line size may have to be
increased beyond the minimum required sizes - see Gas Line Sizing on page 37.
taBle 3
u. s. gallons/hr & liters/hr at temperature rise indicated
model
Type of
Gas
Input
°F
20°F
30°F
40°F
50°F
60°F
70°F
80°F
90°F
100°F 110°F 120°F 130°F 140°F
btu/hr
kW
°C
11°C
17°C
22°C
28°C
33°C
39°C
44°C
50°C
56°C
61°C
67°C
72°C
78°C
bTH 300
Natural
300,000
88
GPH
1746
1164
873
699
582
499
436
388
349
318
291
269
250
Propane
LPH
6610
4406
3304
2644
2203
1888
1652
1469
1322
1201
1102
1017
945
bTH 400
Natural
399,900
117
GPH
2328
1552
1164
931
776
665
582
517
466
423
388
359
332
Propane
LPH
8813
5875
4406
3525
2938
2518
2203
1958
1763
1602
1469
1356
1259
bTH 500
Natural
499,900
146
GPH
2878
1919
1439
1151
959
822
720
640
576
523
480
443
411
Propane
LPH
10894
7263
5447
4358
3631
3113
2724
2421
2179
1981
1816
1676
1556
recovery capacities are based on 96% thermal efficiency for BTH 300, BTH 400 and 95% thermal efficiency for BTH 500.
installation considerations
35°
20°
70°
18°
45°
45°
CL
EA
NO
UT
T &
P
VA
LV
E
G
AS
*1 1/2” NPT
WATER
OUTLET
FRONT
TOP
DRAIN V
AL
VE
INTAKE AIR
4 INCH PVC
VENT
4 INCHPVC
FRONT
BACK
CLEANOUT
T & P
3/4” NPT
DRAIN
1 1/2” NPT
WATER INLET
4” PVC
VENT CONNECTION
(exhaust elbow)
4” PVC
INTAKE AIR
CONNECTION
1 1/4” SUPPLY GAS
CONNECTION
33.12” (84.1 cm)
OUTSIDE
DIAMETER
4.86”
(12.34 cm)
50.77”
(129 cm)
75.50”
(191.8 cm)
69”
(175.3 cm)
69”
(175.3 cm)
12”
(30.5 cm)
* Center line of water outlet on top of the water heater is 7 inches from the front edge of the water heater.
WATER
OUTLET
HEIGHT
63 INCHES
(160 cm)
CONDENSATE
DRAIN CONNECTION
1/2 INCH PVC
recoVery capacities