13

Mixing valves are available at plumbing supply stores. Consult 
a Qualifi ed Installer or Service Agency. Follow the mixing valve 
manufacturer’s instructions for installation of the valves.

  TABLE 5

CONTAMINATED WATER

This HPWH unit must not be used to heat any fl uid other than 
water. Corrosive chemicals must not be introduced into the 
waterways in this HPWH unit.

TEMPERATURE-PRESSURE RELIEF VALVE 

This heat pump water heater should only be connected to 
a storage tank with a properly rated/sized and certified 
combination temperature - pressure relief valve. The valve 
must be certifi ed by a nationally recognized testing laboratory 
that maintains periodic inspection of production of listed 
equipment of materials as meeting the requirements for Relief 
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, 
and the code requirements of ASME.

When the HPWH unit is connected to a storage tank a 
temperature and pressure relief valve must be installed in the 
designated opening for the T&P valve per the storage tank 
manufacturer’s requirements. The T&P valve’s Btu/hr rating 
must be equal to or greater than the total heating input rating 
of all water heaters connected to the storage tank. If more 
than one water heating unit is connected to the storage tank 
the aggregate total of all heating input ratings of all connected 
unit must be factored when choosing a T&P valve for the 
storage tank.

The pressure rating of the T&P valve should always be rated 
equal to or below the working pressure rating of the storage 
tank or water heater, whichever rating is lower.

Contact the manufacturer of the storage tank for assistance 
in sizing of a temperature and pressure relief valve. Follow the 
storage tank manufacturer’s instructions regarding the proper 
installation of these products.

TANK SELECTION

The HPWH unit is not an instantaneous water heater and must 
be connected to a storage tank. Storage tank confi gurations 
must meet these criteria:

1.  The HPWH must not be connected directly to a standard 

gas or electric water heater.

2.  If the HPWH is connected to a used storage tank, the tank 

should be thoroughly cleaned of scale and sediment before 
the HPWH is installed.

3.  Connection ports used on the storage tank must permit 

the recommended fl ow rate through HPWH. The connection 
ports used on the storage tank must not be smaller than 
the inlet outlet connection sizes on the HPWH unit. See 
Table 4 on page 12.

4.  Water heated by the HPWH should be returned to the 

tank at a location that is above the level of the tank’s cold 
water inlet and/or the heat pump’s inlet source.

5.  The HPWH unit’s inlet and outlet lines to the storage tank 

should be dedicated. Example: no other line (such as a 
building re-circulating loop or cold water supply) should 
be connected to the HPWH unit’s inlet or outlet water 
lines.

SOLAR TANKS

Solar tanks should be used with caution. Some solar tanks 
with top connections have dip tubes which may signifi cantly 
reduce the effi

  ciency performance of the HPWH unit. 

Before using any solar tank in this application, contact your 
representative or call the toll free technical support number 
on the back cover of this manual for further assistance.

Potentially harmful fumes and vapors could be introduced 
into occupied spaces. See Unit Placement on page 15.

STORAGE & HANDLING

The heat pump water heaters covered in this manual are 
stationary refrigeration units. Careful handling is necessary to 
prevent internal damage.

Summary of Contents for AHPM-270

Page 1: ...ion Manual Series 100 Models AHPM 270 AHPM 540 AHPM 810 AHPM 1080 AHPM 1350 AHPM 1620 AHPM 1890 AHPM 2160 Modular Water Source Commercial Heat Pump Water Heating Systems Certified UL 1995 2015 CSA C22...

Page 2: ......

Page 3: ...O MEMBER UNITS 22 MASTER CONTROL UNIT SUPPORT CALL SEQUENCE OF OPERATIONS 22 MEMBER SCREENS 23 SAFE INSTALLATION USE AND SERVICE 1 GENERAL SAFETY INFORMATION 2 PRECAUTIONS 2 GROUNDING INSTRUCTIONS 2 I...

Page 4: ...DDRESS CONFIGURATION 23 SINGLE UNIT HEAT BANK SCREEN 23 MEMBER SCREEN TERMINOLOGY 24 HOME SCREEN 24 ALARM SCREEN 24 CONFIGURATION SCREEN 24 STOP SCREEN 24 IP CONFIGURATION 24 MAINTENANCE AND SERVICE 2...

Page 5: ...hers who install use or service this heat pump water heater All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoi...

Page 6: ...External fire 2 Damage 3 Running without water GROUNDING INSTRUCTIONS This heat pump water heater must be grounded in accordance with the National Electrical Code and or local codes These must be foll...

Page 7: ...AGE Thismanualcontainsinstructionsfortheinstallation operation and maintenance of the heat pump water heater HPWH It also contains warnings throughout the manual that you must read and be aware of All...

Page 8: ...ustomer provided Water Pump circulates water through the condenser Refrigerant leaving the condenser is a medium temperature high pressure liquid It flows through the Liquid Line to the Thermostatic E...

Page 9: ...Circuit Heated Water Inlet Condenser Heat Exchanger Heated Water Outlet Figure 1 FEATURES COMPONENTS PRODUCT ILLUSTRATION Component Source Water Circuit Source Water Inlet Evaporator Heat Exchanger S...

Page 10: ...6 Thermostatic Expansion Valve TXV Condenser Paddle Wheel Flow Sensor Accumulator Receiver...

Page 11: ...7 WATER TO WATER CYCLE...

Page 12: ...H AHPM 270 50 50 277 100 210 000 2 34 36 68 1 150 1 300 AHPM 540 100 100 554 200 414 450 2 64 36 68 2 300 2 600 AHPM 810 150 150 831 300 632 500 2 99 36 68 3 450 3 900 AHPM 1080 200 200 1 108 400 843...

Page 13: ...st conform to these instructions and all local and national code authority having jurisdiction Costs to diagnose perform service and repair damage caused by installation errors are not covered under t...

Page 14: ...0 or the Canadian Electrical Code CSA C22 1 Voltage applied to the HPWH should not vary more than 5 to 10 of the voltage requirement listed on the HPWH rating label for satisfactory operation TABLE 2...

Page 15: ...e heat pump water heaters are two wire circuits Three phase heaters are three wire circuits In addition to the foregoing a grounded conductor is required Not more than three conductors in raceway cabl...

Page 16: ...ion to using the lowest possible temperature setting that satisfies the demand of the application a Mixing Valve should be installed upstream from the building fixtures or at the hot water taps to fur...

Page 17: ...sistance in sizing of a temperature and pressure relief valve Follow the storage tank manufacturer s instructions regarding the proper installation of these products TANK SELECTION The HPWH unit is no...

Page 18: ...omponents are not moisture tolerant Note The limited warranty does not cover damage to the unit or controls due to negligence during storage The pictures may appear different than your actual unit all...

Page 19: ...g channels on the bottom of the unit See Table 1 on page 8 for unit dimensions and weights Note A qualified engineer should design and size the structural components of the mounting frame Structural c...

Page 20: ...ntrolled by a field supplied thermostat installed in the building recirculation return line near the storage tank or back up heater The thermostat should stop pump operation the moment the recirculati...

Page 21: ...line on the HPWH to help prevent scale build up in the heat exchanger Service costs to clear blockages from the HPWH unit s heat exchanger due to debris are not covered under the limited warranty ELEC...

Page 22: ...ey on the Touchscreen Monitor the refrigerant pressure hot water in and out temperatures and cold water in and out temperatures Itmaybehelpfultorecordtheoperatingdatainitiallyevery10 to15minutesjustto...

Page 23: ...ince they will always start and run in the proper direction Three phase compressors will rotate in either direction depending upon phasing of the power to L1 L2 and L3 Since there is a 50 50 chance of...

Page 24: ...inimum of water piping between the HPWH and the water system or tank Throttling should be done in small increments no more than 1 8 turn of the valve handle at a time The HPWH must be allowed to run f...

Page 25: ...TER PANEL ALARM SCREEN MASTER PANEL CONFIGURATION SCREEN MASTER SCREEN TERMINOLOGY HOME SCREEN LP Low Pressure indicates the suction line pressure on the low side of the system HP High Pressure indica...

Page 26: ...pDiff Temperature Difference sets the difference below the setpoint where the master will give a call for members to run SAVE button Saves the Tank Diff Set and System Timer parameters Master IP Addre...

Page 27: ...ME SCREEN OPERATING AS A SINGLE UNIT IN DEFROST SINGLE UNIT HOME SCREEN DISPLAYING ALARM SINGLE UNIT ALARM SCREEN SINGLE UNIT PIPE CONFIGURATION SCREEN SINGLE UNIT TANK CONFIGURATION SCREEN SINGLE UNI...

Page 28: ...n short cycling OUTLET FLOW indicates if the unit has alarmed out on condenser water flow Evap Flow indicates if the evaporator has flow M PROTECTION indicates if the unit has alarmed out on motor pro...

Page 29: ...l from the insulation using a vacuum device with a HEPA filter 99 97 efficient at 0 3 micron particles Be careful not to tear the insulation during the cleaning procedure 4 Apply the microbial cleanin...

Page 30: ...ould be 8 F to 12 F 4 4 C to 6 7 C BRAZE PLATE CLEANING INSTRUCTIONS In some applications the heat exchanger may be subjected to severe fluid conditions including high temperature hard water condition...

Page 31: ...d Shut off valves are partially closed Thermostat setting should not exceed 160 F Keep heat pump off until room temperature is back in operating range Low water ow corrections Replace unit pump Reduc...

Page 32: ...K ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER THERMAL...

Page 33: ...TION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO HP WATER HEATER THERMOWELL THERMAL STORAGE...

Page 34: ...GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING ONLY USE BOTTOM LOWER CONNECTION IF TANK HAS TWO THERMOWELL HP WATER HEATER HP WATER HEATER MASTER CONTROL PANEL RECOMMENDED FOR MU...

Page 35: ...HECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING HP WATER HEATER THERMOWELL THERMAL STORAGE COLD WATER SUPPLY...

Page 36: ...SINGLE HEATER MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOURCE WATE...

Page 37: ...HEATER REVERSE RETURN MIXING VALVE CHECK VALVE EXPANSION TANK ISOLATION VALVE CIRCULATING PUMP TEMPERATURE GAUGE WYE STRAINER TEMP PRESS RELIEF VALVE FLUSH VALVE PIPING WIRING SOURCE WATER SUPPLY SOUR...

Page 38: ...en the heat pump water heater is installed in accordance with local plumbing and building codes ordinances and regulations the warrantor s printed instructions provided with it and good industry pract...

Page 39: ...35 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 1 833 447 3201 www hotwater com...

Page 40: ...36 Service Log Issue Description Date Servicer...

Page 41: ...Service Log Issue Description Date Servicer 37...

Page 42: ...Notes 38...

Page 43: ......

Page 44: ......

Reviews: