If a water heater is installed in a closed water system, contact the
water supplier or local plumbing inspector on how to control this
situation.

WATER (POTABLE) HEATING AND

SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, shall

NEVER be introduced into this system.

3. This unit may NEVER be connected to any existing heating

system or component(s) previously used with a non-potable
water heating appliance.

4. When the system requires water for space heating at

temperatures higher than required for domestic water
purposes, a tempering valve must be installed.  Please refer
to installation diagrams on pages 16 through 21 in this manual
for suggested piping arrangements.

 CAUTION

A closed system will exist if a check valve (without bypass),
pressure reducing valve (without bypass), or a water meter (without
bypass) is installed in the cold water line between the water heater
and street main (or well).

Excessive pressure may develop in such closed systems, causing
premature tank failure or intermittent relief valve operation.  This
is not a warranty failure.  An expansion tank or a similar device
may be required in the inlet supply line between the appliance
and the meter or valve to compensate for the thermal expansion
of the water.

SYSTEM CONNECTIONS

The system installation must conform to these instructions and to
the local code authority having jurisdiction.  Good practice requires
that all heavy piping be supported.

THERMOMETERS (Not Supplied)

Thermometers should be obtained and field installed as shown in
the installation diagrams.

Thermometers are installed in the system as a means of detecting
the temperature of the outlet water supply.

RELIEF VALVE

This water heater is equipped with a combination temperature-
pressure relief valve that complies with the standard for relief
valves and automatic gas shut-off devices for hot water supply
system, ANSI Z21.22-CSA 4.4. 

FOR SAFE OPERATION OF THE

WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE
REMOVED OR PLUGGED.

ASME ratings cover pressure relief capacities. ANSI ratings cover
release rate with temperature actuation.

In addition to the appliance relief valve, each remote storage tank
which may be used in conjunction with this appliance shall also

be installed with a properly sized, rated and approved combination
temperature (ANSI) and pressure (ASME) relief valve(s).

 

WARNING

THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE,
WHICH MAY CAUSE SCALDING AT FIXTURES, TANK
EXPLOSION, SYSTEM OR HEATER DAMAGE.  NO VALVE IS
TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.

Your local code authority may have other specific relief valve
requirements.

A DRAIN LINE MUST BE CONNECTED TO THE RELIEF
VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO
AVOID SCALDING OR WATER DAMAGE.  THIS LINE MUST
NOT BE REDUCED FROM THE SIZE OF THE VALVE OUTLET
AND MUST NOT CONTAIN VALVES, RESTRICTIONS NOR
SHOULD IT BE LOCATED IN FREEZING AREAS.  DO NOT
THREAD OR CAP THE END OF THIS LINE.  RESTRICTED
OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE
OF THE VALVE AND IS UNSAFE.  DISCHARGE LINE SHALL
BE INSTALLED TO ALLOW COMPLETE DRAINAGE OF BOTH
THE VALVE AND LINE.

See SERVICE INFORMATION section for procedure and
precautions.

GAS PIPING

Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation codes
for your area.

Size the main gas line in accordance with Table 4.  The figures
shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop,
which is considered normal for low pressure systems.  

Note:

Fittings such as elbows, tees and line regulators will add to
the pipe pressure drop.  Also refer to the current edition of the
National Fuel Gas Code. For Canadian installations consult
Natural Gas and Propane Installation Code CAN/CSA-B149.1.

TABLE 4 - GAS SUPPLY LINE SIZES (IN INCHES)*

MAXIMUM CAPACITY OF PIPE IN

CUBIC FEET PER HOUR

LENGTH

NOMINAL IRON PIPE SIZES (INCHES)

IN

FEET

1/2” 3/4”

1” 1 1/4” 1 1/2”

2”

2 1/2”

3”

4”

10

175

360

680 1400

2100 3960 6300 11000 23000

20

120

250

465

950

1460 2750 4360

7700 15800

30

97

200

375

770

1180 2200 3520

6250 12800

40

82

170

320

660

990

1900 3000

5300 10900

50

73

151

285

580

900

1680 2650

4750

9700

60

66

138

260

530

810

1520 2400

4300

8800

70

61

125

240

490

750

1400 2250

3900

8100

80

57

118

220

460

690

1300 2050

3700

7500

90

53

110

205

430

650

1220 1950

3450

7200

100

50

103

195

400

620

1150 1850

3250

6700

125

44

93

175

360

550

1020 1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

 WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 14.0" W.C.(3.5 kPa) (1/2 POUND PER SQUARE INCH

Summary of Contents for BTR 120

Page 1: ...nnessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROU...

Page 2: ...3 4 59 00 8 30 25 1 50 2 00 2 00 1 50 2 00 2 00 760 Lbs 874 Lbs 114 kW Hr 379 L 192 cm 12 cm 171 cm 148 cm 68 cm 58 cm 3 4 150 cm 20 cm 77 cm 1 50 2 00 2 00 1 50 2 00 2 00 345 Kg 396 Kg BTRC MODELS 1...

Page 3: ...1031 957 BTR 390 000 BTUH 100 Gal 80 1293 970 776 646 554 485 431 388 353 323 298 277 400 114 Kw Hr 379 L 4894 3671 2936 2447 2097 1835 1631 1468 1335 1224 1129 1049 TABLE 1D HEATER PERFORMANCE DATA B...

Page 4: ...ooting Guide 33 Operational Checklist 34 Limited Warranty 35 Page Page FOREWORD These designs comply with ANSI Z21 10 3 CSA 4 3 as an automatic circulating or automatic storage tank type water heater...

Page 5: ...explosive and heavier than air It collects first in the low areas making its odor difficult to detect at nose level If LP gas is present or even suspected do not attempt to find the cause yourself Go...

Page 6: ...or operation at altitudes other than that specified on the heater rating plate is not permitted The input reduction is primarily achieved by reducing the size of the main burner orifices To do this th...

Page 7: ...AUTOMATIC OPERATION and HOLD OPEN DAMPER For normal operation the switch should be in the AUTOMATIC OPERATION position If there is a problem with the damper the Service Switch can be placed in the HOL...

Page 8: ...g must be a continuous run no joints and retain the 6 16cm clearance unless an approved reducing thimble is used The National Sanitation Foundation also recommends circulation of 180 F 82 C water Wher...

Page 9: ...NAIR CONTAMINATIONTHATMAYBE HAZARDOUS TOLIFE SUCHACONDITIONOFTENWILLRESULTINAYELLOW LUMINOUSBURNERFLAME CAUSINGCARBONINGORSOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATESARISK OFAS...

Page 10: ...S OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with the...

Page 11: ...BTR C 180 197 198 199 200 Input 180 000 190 000 199 000 Btuh Total Vent Height Feet Draft Hood 6 6 8 10 15 20 30 50 100 Input Btuh Rise Vent Connector Diameter in inches 180 000 1 Ft 8 8 8 8 8 7 7 7...

Page 12: ...10 10 10 8 8 8 Number of Combined Input Heaters in Thousands of Btuh Manifold Common Vent Diameter 2 610 14 14 12 12 12 10 10 10 3 915 16 16 16 14 14 12 12 12 4 1220 18 18 16 16 16 14 14 12 MODEL BTR...

Page 13: ...used in conjunction with this appliance shall also be installed with a properly sized rated and approved combination temperature ANSI and pressure ASME relief valve s WARNING THE PURPOSE OF RELIEF VA...

Page 14: ...AND CERTIFIED FOR GAS SERVICE BEFOREATTACHING THE GAS LINE BE SURE THATALL GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIM...

Page 15: ...SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 5 kPa GAS SUPPLY LINE MUSTBE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF 1 2 PSIG 3 5 kPa OR LESS THE APPLIANCE NEED NOT BE DISCONNECTED...

Page 16: ...ULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROLWARNING ON PAGE 27 IF HIGHER PREHEAT TEMPERATURESARE NECESSARY TO OBTAINADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 17: ...MUST BE CLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACH...

Page 18: ...wn in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of the tem...

Page 19: ...OTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Page 20: ...ERS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 27 IF HIGHER PREHE...

Page 21: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Page 22: ...OD A BTR MODELS BTRC MODELS 120 69 75 177cm 69 75 177cm 154 73 00 185cm 73 00 185cm 180 67 50 171cm 70 50 179cm 197 75 00 192cm 81 50 207cm 198 75 00 192cm N A 199 67 50 171cm 70 50 179cm 200 72 00 18...

Page 23: ...ete instructions MULTIPLE UNIT INSTALLATIONS For multiple unit installations contact A O Smith Water Products Company Technical Support Center at 1 800 527 1953 In Canada contact A O Smith Enterprises...

Page 24: ...AVOID RISK OF FIRE OR EXPLOSION PURGE DISCHARGE MUST NOT ENTER CONFINEDAREAS OR SPACES WHERE IGNITION CAN OCCUR THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION MUSTBE INACTIVATED OR REMOV...

Page 25: ...25 FOR NATURAL GAS MODELS...

Page 26: ...26 FOR PROPANE GAS MODELS...

Page 27: ...e water temperature is controlled by a thermostat Fig 3 which has two sensing elements One sensor is located near the top of the tank and the other is near the center The thermostat is set in the lowe...

Page 28: ...MAINTENANCE CHECK THE PILOT At least once a year check the pilot burner fig 15 and the main burner fig 16 for proper operation Refer to the following pilot and main burner sections PILOT BURNER For a...

Page 29: ...pressure gauge or a manometer to the gauge port and refer to Table 5 for correct manifold pressure 2 Use this formula to clock the meter Be sure that other gas consuming appliances are not operating...

Page 30: ...he heater and replacement of the factory installed magnesium anodes with aluminum anodes may correct the condition Occasionally water softener companies recommend removal of heater anodes for odor rea...

Page 31: ...screws securing tank cleanout plate and remove plate 4 Remove lime scale or sediment using care not to damage the glass lining 5 Inspect cleanout plate gasket if new gasket is required replace with A...

Page 32: ...e replaced TROUBLESHOOTING IGNITION MODULE SYSTEM Before calling your service agent the following checklist should be examined to eliminate obvious problems from those requiring replacement or servici...

Page 33: ...Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into appliance receptacle A FLUE DAMPER OPEN OR OPENING Unit is calling for heat and damper disc should be in vertical posi...

Page 34: ...slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Draft hood not installed or Call serviceman Install draft hood or baffles as one or more flue ba...

Page 35: ...e heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 527 1953 Fax 800 433 2515 www hotwater com...