background image

10

BOILER START UP AND OPERATIONS

After placing the boiler into operation, the ignition system safety 

shutoff device must be tested by the following test method

.

1. 

Reset  High  Limit  Temperature  Control  to  lowest  setting. 

 

(See Figure 2 on Page 7).

2. 

Reset System Controller to maximum setting, causing a call 

for heat and allowing unit to run until High Limit Temperature 

Control trips.

3. 

Resetting  the  High  Limit  Temperature  Control  to  a  higher 

setting, unit should run.

4. 

Reset  System  Controller  and  High  Limit  Temperature 

Control to desired temperature. If unit fails to run, refer to 

Troubleshooting section in this manual on Page 16.

Before operating the boiler, the entire system must be filled with 

water, purged of air and checked for leaks. Do not use Stop Leak 

or other boiler compounds. The gas piping should also be leak 

tested.
Any safety devices including low water cutoffs used in conjunction 

with  this  boiler  should  receive  periodic  (every  six  months) 

inspection to assure proper operation. A low water cutoff device 

of the float type should be flushed every six months. All pressure 

relief valves should be inspected and manually operated at least 

twice a year.

IMPORTANT

It is recommended that a qualified service technician perform 

the initial firing of the boiler. At this time the user should not 

hesitate to ask the individual any questions which he may 

have in regard to the operation and maintenance of the unit.

FILLING THE SYSTEM

1. 

Fast fill system through bypass until pressure approaches 

desired  system  pressure.  Close  bypass  valve  and  permit 

pressure to be established by the pressure reducing valve.

2. 

Vent all high points in system to purge system of air.

If pressure bleeding of system is desired, install valves as shown 

in the Piping Diagrams of the Instruction Manual.
Where  cast  iron  radiation  and  motorized  valves  are  used, 

conventional system pressure and installation practices should 

be followed.

Provisions should be made to permit manual venting of radiators 

or convectors.

PRECAUTIONS

If  the  unit  is  exposed  to  the  following,  do  not  operate  boiler 

until all corrective steps have been made by a qualified service 

technician:

•  Flooding to level of burner or controls or higher.
•  Exposure to fire.
•  If damaged.
•  Firing without water.
• 

Sooting.

PILOT AND MAIN BURNER

To  maintain  safe  operation  of  the  boiler,  check  the  pilot  and 

the  main  burner  once  every  six  months  for  proper  flame 

characteristics.

1. 

MAIN BURNER

The  main  burner,  Figure  6,  should  display  the  following 

characteristics:

•  Provide complete combustion of gas.
•   Cause rapid ignition and carryover of flame across entire 

burner.

•   Give reasonably quiet operation during ignition, burning 

and extinction.

•   Cause no excessive lifting of flame from burner ports.

If the proceeding burner characteristics are not evident, check 

for accumulation of lint or other foreign material that restricts or 

blocks the air openings to the burner or boiler.
Also check for good flow of combustion and ventilating air to the 

unit. Maintain a clear area around the boiler at all times.

The boiler should be periodically inspected by a qualified servicer 

for continuous safe operation.
Qualified servicers should follow this procedure when the boiler’s 

burners need cleaning.

a. 

Turn off the electrical power and close the main manual gas 

shutoff valve. Refer to Lighting & Operating Instructions on 

Pages 14 and 15.
•  Allow boiler parts to cool before disassembly.

b. 

Remove main burner manifold assembly from boiler.
•  Refer to parts list supplied with this manual for 

disassembly aid.

c.  Remove any loose foreign material such as dust or lint with 

a  vacuum.  Check  all  ports,  orifices,  and  air  openings  for 

blockage. Dislodge any foreign material causing blockage. 

Remove any soot or carbon deposits with a rag making sure 

to remove any lint left on burner by vacuuming again.

d.  Reinstall the burner manifold assembly on boiler.

e. 

Restore electrical power and gas supply to boiler.
•  Put the boiler back in operation by following the lighting 

instructions in this manual or on the lighting and 

operating label on the boiler. Refer to Pages 14 and 15.

•  Check for gas leaks and proper boiler and vent operation.

FIGURE 6.  MAIN BURNER

Summary of Contents for Burkay HW-300

Page 1: ...exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applian...

Page 2: ...OMPONENTS 6 BOILER START UP AND OPERATIONS 10 Filling the system 10 Precautions 10 Pilot and main burner 10 Checking and adjusting input 12 TROUBLESHOOTING 16 MAINTENANCE PROCEDURES 24 Manual reset hi...

Page 3: ...y hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...l Code CSA C22 1 ABBREVIATIONS USED Abbreviations found in this Instruction Manual include ANSI American National Standards Institute ASME American Society of Mechanical Engineers NEC National Electri...

Page 6: ...6 Figure 1 COMPONENT LOCATIONS CONTROL COMPONENTS...

Page 7: ...push the reset button The high limit switch may be reset after the coil surface cools to 6 F 3 3 C below the trip setting AUTO RESET HIGH LIMIT The high limit is a safety device wired in series with t...

Page 8: ...h ASME code Properly sized Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death Water Damage Hazard Press...

Page 9: ...lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies the user s hot water...

Page 10: ...iators or convectors PRECAUTIONS If the unit is exposed to the following do not operate boiler until all corrective steps have been made by a qualified service technician Flooding to level of burner o...

Page 11: ...ee Figure 7 Check for good terminal connection at the sensing probe at the pilot burner assembly if pilot does not light Check for electrical power to the valve If electrical power and gas are present...

Page 12: ...this formula to clock the meter Be sure that other gas consuming appliances are not ON during this interval 3600 x H Btuh T Btuh The approximate actual input rate T Time in seconds to burn one cubic f...

Page 13: ...M After 15 sec ignition shut down 5 minute time delay before re try S 8600H After 15 sec ignition system locks out must be manually reset FLAME CURRENT SENSED Spark generator off Second valve operator...

Page 14: ...14 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE FOR HW300 HW399...

Page 15: ...15 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE WITH I I D FOR HW420 UP...

Page 16: ...ff delay of approximately 2 minutes Pump and burner remain on Tank temperature control thermostat defective Replace System wiring is incorrect Correct wiring Circulating pump on Pump wired for continu...

Page 17: ...ceramic insulator surrounding the electrode cracked or broken Replace pilot burner assembly Replace ignition module Turn on gas supply Turn on power supply Securely connect cable and or ground wire Ca...

Page 18: ...ttached to pilot assembly and GND terminal on module Are ignition cable and ground wire in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor ro...

Page 19: ...sensor rod in good condition not broken or cracked Is the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the inst...

Page 20: ...lot ground wire firmly attached to the pilot assembly and GND terminal on module Are high voltage cable and ground wire in good condition not brittle burnt or cracked Make sure pilot flame spreader ho...

Page 21: ...below minimum threshold for system operation not applicable A Flash Code Descriptions Heartbeat Constant 1 2 second bright 1 2 second dim cycles The flash code number signifies that the LED flashes X...

Page 22: ...ontrol remains in wait mode When the fault corrects control resumes normal operation after a one minute delay Check transformer and AC line for proper input voltage to the control Check with full syst...

Page 23: ...r proper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled Check gas supply...

Page 24: ...r bad leads With leads attached depress the switch button If the meter does not read zero the switch is defective and must be replaced PRESSURE RELIEF VALVE TEST Burn hazard Hot water discharge Keep c...

Page 25: ...w boiler parts and vent to cool before disassembly 2 Remove the boiler draft diverter and vent pipe running to the chimney Check parts and chimney for obstructions and clean as necessary 3 Remove burn...

Page 26: ...26 NOTES...

Page 27: ...te or provincial law are limited to one 1 year dura tion for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limita...

Page 28: ...28 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: