background image

16

TABLE 3.  CER-TEMP 80 RECOVERY SYSTEM CHECKOUT PROCEDURE

Before any extensive troubleshooting, perform the following:
Ensure that:

•  Voltage (120 vac) is supplied to the boiler.
•  System control (tank temperature control, thermostat, 

etc.) is calling for boiler operation (call for heat).

•  Other contacts (switches) are closed (relay, low water 

cutoff, flow switch, coil protector, pressure switch, etc.).

•  Gas supply pressure is within the maximum and minimum 

operating ranges listed on the boiler rating plate/label.

•  Voltage (24 vac) is supplied by transformer.
•  Boiler is wired according to wiring diagram.

Note: Cross wiring the 24 volt circuit of the relay will short the 

transformer.

•  All wire terminals/connectors are firmly attached to 

valves, modules, switches, limit controls, etc.

•  For Propane (LP) models only check for possible lockout 

condition of the ignition module.

Use this checkout for Cer-Temp 80 Recovery Systems. (For hot water supply application only)

CHECKOUT SEQUENCE

SYSTEM OPERATION

CAUSE

REMEDY

CORRECT

INCORRECT

Set tank temperature 

control (thermostat) 

20°F (10°C) below tank 

water temperature.

Circulating pump and 

burner shut off.

With thermal balancer, 

pump off delay of 

approximately 2 minutes.

Pump and burner remain 

on.

Tank temperature control 

(thermostat) defective.

Replace.

System wiring is 

incorrect.

Correct wiring.

Circulating pump on.

Pump wired for 

continuous operation.

Correct wiring.

Burner on.

Gas control valve stuck 

or defective.

Correct or replace 

valve.

System wiring is 

incorrect.

Correct wiring.

Set tank temperature 

control (thermostat) 

20°F (10°C) above tank 

water temperature.

Circulating pump and 

burner on.

Circulating pump on.

High limit control set too 

low.

Replace. (If 

problem proven to 

be at this control by 

applying jumper to 

terminals.)

High limit control 

differential too wide.

System wiring is 

incorrect.

Correct wiring.

Coil protector switch has 

activated.

Remove control 

cover, depress 

reset button.

Gas control valve or 

wiring defective.

Check wiring. 

Repair or replace 

valve.

Circulating pump and 

burner off.

Power off or system 

wiring is incorrect.

Check power supply 

and wiring.

Tank temperature control 

(thermostat) defective.

Replace.

Burner on.

System wiring is 

incorrect.

Correct wiring.

Boiler outlet 

temperature exceeds 

210°F (100°C).

Circulating pump on.

Circulating pump and 

burner on.

High limit control 

defective, or set too high 

(max. should be set at 

200°F).

Replace.

Set tank temperature 

control (thermostat) 

for desired water 

temperature.

System maintains desired 

water temperature.

TROUBLESHOOTING

Summary of Contents for Burkay HW-300

Page 1: ...exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applian...

Page 2: ...OMPONENTS 6 BOILER START UP AND OPERATIONS 10 Filling the system 10 Precautions 10 Pilot and main burner 10 Checking and adjusting input 12 TROUBLESHOOTING 16 MAINTENANCE PROCEDURES 24 Manual reset hi...

Page 3: ...y hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...l Code CSA C22 1 ABBREVIATIONS USED Abbreviations found in this Instruction Manual include ANSI American National Standards Institute ASME American Society of Mechanical Engineers NEC National Electri...

Page 6: ...6 Figure 1 COMPONENT LOCATIONS CONTROL COMPONENTS...

Page 7: ...push the reset button The high limit switch may be reset after the coil surface cools to 6 F 3 3 C below the trip setting AUTO RESET HIGH LIMIT The high limit is a safety device wired in series with t...

Page 8: ...h ASME code Properly sized Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death Water Damage Hazard Press...

Page 9: ...lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies the user s hot water...

Page 10: ...iators or convectors PRECAUTIONS If the unit is exposed to the following do not operate boiler until all corrective steps have been made by a qualified service technician Flooding to level of burner o...

Page 11: ...ee Figure 7 Check for good terminal connection at the sensing probe at the pilot burner assembly if pilot does not light Check for electrical power to the valve If electrical power and gas are present...

Page 12: ...this formula to clock the meter Be sure that other gas consuming appliances are not ON during this interval 3600 x H Btuh T Btuh The approximate actual input rate T Time in seconds to burn one cubic f...

Page 13: ...M After 15 sec ignition shut down 5 minute time delay before re try S 8600H After 15 sec ignition system locks out must be manually reset FLAME CURRENT SENSED Spark generator off Second valve operator...

Page 14: ...14 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE FOR HW300 HW399...

Page 15: ...15 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE WITH I I D FOR HW420 UP...

Page 16: ...ff delay of approximately 2 minutes Pump and burner remain on Tank temperature control thermostat defective Replace System wiring is incorrect Correct wiring Circulating pump on Pump wired for continu...

Page 17: ...ceramic insulator surrounding the electrode cracked or broken Replace pilot burner assembly Replace ignition module Turn on gas supply Turn on power supply Securely connect cable and or ground wire Ca...

Page 18: ...ttached to pilot assembly and GND terminal on module Are ignition cable and ground wire in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor ro...

Page 19: ...sensor rod in good condition not broken or cracked Is the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the inst...

Page 20: ...lot ground wire firmly attached to the pilot assembly and GND terminal on module Are high voltage cable and ground wire in good condition not brittle burnt or cracked Make sure pilot flame spreader ho...

Page 21: ...below minimum threshold for system operation not applicable A Flash Code Descriptions Heartbeat Constant 1 2 second bright 1 2 second dim cycles The flash code number signifies that the LED flashes X...

Page 22: ...ontrol remains in wait mode When the fault corrects control resumes normal operation after a one minute delay Check transformer and AC line for proper input voltage to the control Check with full syst...

Page 23: ...r proper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled Check gas supply...

Page 24: ...r bad leads With leads attached depress the switch button If the meter does not read zero the switch is defective and must be replaced PRESSURE RELIEF VALVE TEST Burn hazard Hot water discharge Keep c...

Page 25: ...w boiler parts and vent to cool before disassembly 2 Remove the boiler draft diverter and vent pipe running to the chimney Check parts and chimney for obstructions and clean as necessary 3 Remove burn...

Page 26: ...26 NOTES...

Page 27: ...te or provincial law are limited to one 1 year dura tion for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limita...

Page 28: ...28 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: