background image

22

GREEN LED

FLASH CODE 

(X+Y)

A

INDICATES

NEXT SYSTEM ACTION

RECOMMENDED SERVICE  

ACTION

OFF

No "Call for Heat"

not applicable

none

Flash Fast

Startup - Flame sense calibration

not applicable

none

Heartbeat

Normal operation

not applicable

none

2

5 minute Retry Delay

•  Pilot flame not detected during 

trial for ignition

Initiate new trial for ignition after 

retry delay completed.

If system fails to light on next 

trial for ignition check gas supply, 

pilot burner, spark and flame 

sense wiring, flame sensor 

contaminated or out of position, 

burner ground connection.

3

Recycle

•  Flame failed during run

Initiate new trial for ignition. Flash 

code will remain through the ignition 

trial until flame is proved.

If system fails to light on next trial 

for ignition, check gas supply, 

pilot burner, flame sense wiring, 

contamination of flame sensor, 

burner ground connection.

4

Flame sensed out of sequence

If situation self corrects within 10 

seconds, control returns to normal 

sequence. If flame out of sequence 

remains longer than 10 seconds, 

control goes to Flash code 6+4 (see 

below).

Check for pilot flame. Replace 

gas control valve if pilot flame is 

present. If no pilot flame, cycle 

"Call for Heat." If error repeats, 

replace control.

7

Flame sense leakage to ground

Control remains in wait mode. When 

the fault corrects, control resumes 

normal operation after a one minute 

delay.

Check flame sense lead wire for 

damage or shorting. Check that 

flame sensor is in proper position.

Check flame sensor ceramic for 

cracks, damage or tracking.

8

Low secondary voltage supply-

(below 15.5 Vac)

Control remains in wait mode. When 

the fault corrects, control resumes 

normal operation after a one minute 

delay.

Check transformer and AC line 

for proper input voltage to the 

control. Check with full system 

load on the transformer.

6+2

5 minute Retry Delay

•  On every third retry on the same 

"Call for Heat"

Initiate new trial for ignition after 

retry delay completed.

Check gas supply line, pilot 

burner, spark and flame 

sense wiring, flame sensor 

contaminated or out of position, 

burner ground connection.

6+3

On every 6th flame failure during run 

on the same "Call for Heat"

5 minute retry delay, then initiate 

new trial for ignition.

Check gas supply, pilot burner, 

flame sense wiring, contamination 

of flame sensor, burner ground 

connection.

6+4

Flame sensed out of sequence-

longer than 10 seconds

Control waits until flame is no 

longer sensed and then goes to 

soft lockout. Flash code continues. 

Control auto resets from soft lockout 

after one hour.

Check for pilot flame. Replace 

gas control valve if pilot flame 

present. If no pilot flame, cycle 

"Call for Heat." If error repeats, 

replace control.

ON

Soft lockout due to error detected 

during self check sequences

Control auto resets from soft lockout 

after one hour.

Reset by cycling "Call for Heat." If 

error repeats, replace the control.

A

Flash Code Descriptions:

•   Flash Fast: rapid blinking.
•   Heartbeat: Constant 1/2 second bright 1/2 second dim cycles.
•   A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats the 

sequence.

•   X+Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off 

for three seconds, and then repeats the sequence.

TABLE 5.  CONTINUOUS RETRY MODELS C, M, E AND K ONLY - GREEN LED STATUS CODES

Summary of Contents for Burkay HW-300

Page 1: ...exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applian...

Page 2: ...OMPONENTS 6 BOILER START UP AND OPERATIONS 10 Filling the system 10 Precautions 10 Pilot and main burner 10 Checking and adjusting input 12 TROUBLESHOOTING 16 MAINTENANCE PROCEDURES 24 Manual reset hi...

Page 3: ...y hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...l Code CSA C22 1 ABBREVIATIONS USED Abbreviations found in this Instruction Manual include ANSI American National Standards Institute ASME American Society of Mechanical Engineers NEC National Electri...

Page 6: ...6 Figure 1 COMPONENT LOCATIONS CONTROL COMPONENTS...

Page 7: ...push the reset button The high limit switch may be reset after the coil surface cools to 6 F 3 3 C below the trip setting AUTO RESET HIGH LIMIT The high limit is a safety device wired in series with t...

Page 8: ...h ASME code Properly sized Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death Water Damage Hazard Press...

Page 9: ...lower water temperatures be used to avoid the risk of scalding It is further recommended in all cases that the water temperature be set for the lowest temperature which satisfies the user s hot water...

Page 10: ...iators or convectors PRECAUTIONS If the unit is exposed to the following do not operate boiler until all corrective steps have been made by a qualified service technician Flooding to level of burner o...

Page 11: ...ee Figure 7 Check for good terminal connection at the sensing probe at the pilot burner assembly if pilot does not light Check for electrical power to the valve If electrical power and gas are present...

Page 12: ...this formula to clock the meter Be sure that other gas consuming appliances are not ON during this interval 3600 x H Btuh T Btuh The approximate actual input rate T Time in seconds to burn one cubic f...

Page 13: ...M After 15 sec ignition shut down 5 minute time delay before re try S 8600H After 15 sec ignition system locks out must be manually reset FLAME CURRENT SENSED Spark generator off Second valve operator...

Page 14: ...14 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE FOR HW300 HW399...

Page 15: ...15 LIGHTING AND OPERATING INSTRUCTIONS NATURAL AND PROPANE WITH I I D FOR HW420 UP...

Page 16: ...ff delay of approximately 2 minutes Pump and burner remain on Tank temperature control thermostat defective Replace System wiring is incorrect Correct wiring Circulating pump on Pump wired for continu...

Page 17: ...ceramic insulator surrounding the electrode cracked or broken Replace pilot burner assembly Replace ignition module Turn on gas supply Turn on power supply Securely connect cable and or ground wire Ca...

Page 18: ...ttached to pilot assembly and GND terminal on module Are ignition cable and ground wire in good condition not brittle burnt or cracked Ensure ground strap is the closest metal to the igniter sensor ro...

Page 19: ...sensor rod in good condition not broken or cracked Is the igniter sensor rod in good condition not worn corroded sooted or damaged Replace ignition module Correct the situation by consulting the inst...

Page 20: ...lot ground wire firmly attached to the pilot assembly and GND terminal on module Are high voltage cable and ground wire in good condition not brittle burnt or cracked Make sure pilot flame spreader ho...

Page 21: ...below minimum threshold for system operation not applicable A Flash Code Descriptions Heartbeat Constant 1 2 second bright 1 2 second dim cycles The flash code number signifies that the LED flashes X...

Page 22: ...ontrol remains in wait mode When the fault corrects control resumes normal operation after a one minute delay Check transformer and AC line for proper input voltage to the control Check with full syst...

Page 23: ...r proper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in lockout Remain in lockout until Call for Heat is cycled Check gas supply...

Page 24: ...r bad leads With leads attached depress the switch button If the meter does not read zero the switch is defective and must be replaced PRESSURE RELIEF VALVE TEST Burn hazard Hot water discharge Keep c...

Page 25: ...w boiler parts and vent to cool before disassembly 2 Remove the boiler draft diverter and vent pipe running to the chimney Check parts and chimney for obstructions and clean as necessary 3 Remove burn...

Page 26: ...26 NOTES...

Page 27: ...te or provincial law are limited to one 1 year dura tion for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limita...

Page 28: ...28 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: