50
N
OTES
:
1.
Pre
ferred
piping
diagram
.
2.
The
tempera
ture
and
pressure
relie
f valve
se
tting
shall
no
t exceed
pressure
ra
ting
o
f any
componen
t in
the
sys
tem
.
3.
Service
valves
are
shown
for
s
ervicing
uni
t.
Howeve
r,
local
codes
shall
govern
their
usage
.
4.
A. O. S
mi
th
piping
me
thod
is
based
on
50
equivalen
t f
ee
t o
f piping
. B
oiler
placemen
t shall
be
as
close
as
prac
tical
to
th
e
st
orage
tank
. A
ppli
ca
tions
in
ex
cess
o
f t
hese
recommenda
tions
shall
require
a
licensed
engineer
for
design
assis
tance
.
BURK
AY
HW(300-670) -
ONE
TEMPER
ATURE-TWO BOILER/HORIZON
TA
L S
TORAGE
T
ANK
RECOVE
RY
SYSTEM
LEGEND
TEMPER
ATURE & PRESSURE
RELIEF
VA
LVE
PRESSURE RELIEF
VA
LVE
CIRCUL
ATING PUMP
TANK
T
EM
PER
ATURE CONTR
O
L
DRAIN
FUL
L PO
RT
BAL
L
VA
LVE
TEMPER
ATURE GAGE
W
ATER FLOW SWITCH
CHECK
VA
LVE
W
ARNING:
THIS DR
AWING SHOWS SUGGESTED
PIPING CONFIGUR
AT
ION
AND OTHER DEVICES;
CHECK WITH LOCA
L CODES
AND ORDINANCES
FOR
ADDITIONA
L REQUIREMENTS.
EXPANSION TANK
COLD WATER SUPPLY
AOS
STORAGE TANK
HOT WATER TO FIXTURES
ALTERNATE LOCATION
SEDIMENT RISER
SYSTEM RETURN
DE-LIMING TEE
DE-LIMING TEE
FINISHED FLOOR
B
A
B
A
BOILER
MODE
L (HW)
BOILER
PIPING SIZE “A” (INCH)
MANIFOLD PIPING SIZE “B” (INCH)
30
0
1 1/
4
2
399-42
0
1 1/
2
2
520-67
0
2
2 1/2
FIGURE
32.
ONE TEMPERA
TURE - TWO BOILERS/ HORIZONT
AL
ST
ORAGE T
ANK RECOVER
Y SYSTEM