Installation and Service Manual Epsilon-Series
29
Parameter-Mode
PARA
Factory
Description
Range
1
70°C
maximum flow temperature CH
20 - 85°C
2
01
type of CH installation:
radiators; air heating; convectors:
T max. flow 85°C; K factor heating line 2.3; gradient 5°C/min; gear
01
radiators with large surface areas or underfloor heating as additional
heating:
02
under floor heating with radiators as additional heating:
T max. flow 60°C; K factor heating line 1.5; gradient 4°C/min; gear
03
full under floor heating:
T max. flow 50°C; K factor heating line 1.0; gradient 3°C/min; gear
04
3
max.
maximum power CH in kW
min-max
4
00
control principal with on / off thermostat:
100 % on / off thermostat
00
100 % on / off weather dependant
01
5
2.3
heating line K-factor (see also heating line graph)
0.2 - 3.5
6
1.4
heating line exponent (see also heating line graph)
1.1 - 1.4
7
-10
heating line climate zone (see also heating line graph)
-20 - 0
10
0°C
fine adjustment heating line day temperature
-5 to 5°C
11
0°C
fine adjustment heating line night temperature
-5 to 5°C
14
5
gradient speed
0 - 15
15
0
booster after night reduction:
no
00
yes
01
23
-3°C
Frost Temperature
-20 to 10°C
27
0°C
Min. flow temperature
0 to 70°C
31
63°C
Cylinder temperature with external cylinder sensor
40 - 80°C
36
0
Type of three way valve cylinder
VC 2010 / VC 8010
00
VC 6940
01
43
max.
Maximum power DHW in kW
min-max
45
0
No function
00 - 01
48
60%
Minimum pump capacity
25-100 %
49
100%
Maximum pump capacity heating
40-100 %
60
01
Type of communication bus:
Automatic recognition of Bus thermostat
01
OpenTherm
02
n.a.
03
89
00
Address of boiler (do not change)
.
.
.
.
Info-Mode
INFO
F t
D
i ti
INFO
Factory
Description
.
.
.
.
1
°C
flow water temperature T1
4
°C
return water temperature T2
5
°C
DHW temperature T3
7
°C
outside temperature T4
8
°C
flue gas temperature T5
16
%
actual power in %
17
kW
actual power in kW
18
kW
actual load in kW
20
indication bus communication
21
GJ
consumption total in GJ (.. x 33 = .. m
3
)
22
GJ
consumption CH in GJ (.. x 33 = .. m
3
)
23
GJ
consumption DHW in GJ (.. x 33 = .. m
3
)
24
Std
total number of burner run hours
25
Std
number of burner run hours CH
26
Std
number of burner run hours DHW
32
Std
total number of hours counter
37
Std
total number of run hours pump CH and DHW
46
Std
within how many hours is service required
.
.
.