Step 2: Condensate tray
- Remove the plug from the flue gas sensor if present;
- Turn the two short clamping rods (11 and 12) ¼ turn with the hex key and remove
them by pulling them forward;
Note the correct turning direction (red indicator,
fig. 12.3.h)
;
- Lift the exhaust pipe (13) out of the condensate tray (14);
- Press the condensate tray (14) carefully downwards and remove it by pulling it forward;
- Replace the gasket between condensate tray and heat exchanger by a new one;
- Clean the condensate tray with water and a hard brush;
- Check the condensate tray on leaks.
Step 3:
Refitting is done in reverse order.
Note that all gaskets seals completely.
Make sure that during refitting the clamping rods they are put in the right
position. They should be turned vertical.
Always replace all removed gaskets of dismanteled parts during the
maintenance activities.
Put the boiler into operation and check the O
2
(see page 33).
In the event that parts require replacement, use only genuine parts supplied by
A.O. Smith.
Please contact your installer or A.O. Smith for further details. Contact details can be
found on the back page of this manual.
Condensate tray figure 13.3.k