background image

Commercial Gas Boilers

Revised November 2008

PG 3 OF 4

www.hotwater.com

AOSDG25200

OTHER GENESIS

®

FEATURES

FACTORY-INSTALLED CIRCULATING PUMP

Pre-wired, integrally controlled by EMC-5000 control

Adjustable pump time delay allows removal of usable residual 
heat during stand-by cycle, virtually eliminating stand-by heat loss

ASME PRESSURE RELIEF VALVE 125#
FACTORY INSTALLED FLOW SWITCH
ALTERNATE THERMOSTAT TERMINALS (24V)
MANUAL RESET HIGH LIMIT
BLOCKED FLUE SWITCH
BLOCKED INLET SWITCH
AIR PROVING SWITCH

GENESIS

®

OPTIONS

CSD-1 CODE
NEW YORK CODE
CALIFORNIA CODE
ALARM BELL
ALL-BRONZE CIRCULATING PUMP
HARD WATER PUMP
BRONZE HEADERS
STACK RACK
LOW WATER CUT-OFF
EXTENDED VENTING KIT
SEQUENCING CONTROL PANEL (FOR 2-8 BOILERS)
COMBUSTIBLE FLOOR SHIELD
DRY CONTACTS FOR ANY BOILER FAILURE
CUPRO-NICKEL HEAT EXCHANGER
CSA CERTIFIED VENT KIT

GENESIS

®

VENTING VERSATILITY

DIRECT-VENTING

SIDEWALL VENTING

CONVENTIONAL VENTING

For the most current Genesis venting distances/information, 
consult the Genesis Product Manual, available through your local 
A. O. Smith representative, or online at www.hotwater.com.

MODEL

NUMBER

BTU INPUT

PER HOUR

RECOVERY — GALLONS PER HOUR AT °F TEMPERATURE RISE

40°

50°

60°

70°

80°

90°

100°

110°

120°

130°

140°

GW/GWO-300

300,000

761

609

507

435

380

338

304

277

254

234

217

GW/GWO-400

399,900

1014

811

676

580

507

451

406

369

338

312

290

GW/GWO-500

500,000

1268

1015

845

725

634

564

507

461

423

390

362

GW/GWO-650

650,000

1649

1319

1099

942

824

733

659

600

600

507

471

GW/GWO-750

750,000

1902

1522

1268

1087

951

845

761

692

634

585

544

Gas Supply Pressure: 13.8” W.C. maximum natural and propane; 4.5” W.C. minimum natural; 11.0” W.C. minimum propane.
Genesis boilers are approved for installation on noncombustible flooring in an alcove with minimum clearance to combustibles of:
3 inches sides, and back; 3 inches top, front alcove; 6 inches vent.
For installation on combustible flooring use the optional Combustible Floor Kit.
Genesis boilers must be connected to a single phase dedicated line source that is: 120 volts, 60 hertz and 20 amps.