l'I
.I'.,
12$
!„"';"
I
'
"i!
Ll
I NEUTRAL
b
I
IIF
PRI
c'I
ALARM
MR
F
Through
pressure
relief
valve
opening
.
4.
Operate
the
system
for
a minimum
of
1 hour
(to
a maximum
of
24
hours).
As
noted
above,
•
Close
system
inlet
and
outlet
valves
at
the
system
pressure
and
temperature
must
be
g".
•
boiler.
such
that
the
water
does
not
boll.
•
Relieve
pressure
from
boiler
and
remove
p
pressure
relief
valve
from
air
purger.
5.
SYSTEM
MUST
NOW
BE
DRAINED
AND
FLUSHED.
•
Remove
an
amount
of
water
from
the
sys-
tem
approximately
equal
to
the
volume
of
•
Close
the
manual
gas
shutoff
valve
to
cleaning
solution
to
be added.
turn
off
the
burner.
This
will
allow
the
circulator
to
continue
operating
during
•
Add
the
cleaning
solution
to
the
system
the
flushing
procedure.
1,:I
through
the
relief
valve
opening.
Replace
relief
valve.
.
Open
the
cold
water
supply
to
the
sys-
tem.
N
.
•
Open
system
inlet
and
outlet
valves
at
boiler.
•
Connect
a
hose
to
the
boiler
drain
valve,
allow
cleaning
solution
to
flow
to
drain.
I.
3.
Pressurize
the
system.
If
necessary,
open
the
cold
water
supply
valve
and
add
pressure
•
All
cleaner
should
be
removed
after
15
to
to
the
system
so
that
the
water
does
not
boil
20
minutes
of
flushing.
during
the
cleaning
process.
OPERATING
INSTRUCTIONS
LIGHTING
INSTRUCTIONS
CAUTION:
Make
sure
heater
is
filled
with
water
'20v·ª°H
~
before
lighting
pilot.
The
main
(man-
ual)
gas
shutoff
valve
and
pilot
ad-
TONEXTANEL
I)
justing
valve,
}ocated
near
main
------e.
USEDI
guue
burner,
should
be
closed
for
at
least
----
SLACK
--'''å°
YELLOW
~
5
minutes.
-
REO
-ñr
~
raNexrpAnat
BALANCER
>
11F
uSED)
.
Do
not
attempt
to
light
pilot
if gas
odor
is
present.
"°"'"°
P
ALARu
Light
the
unit
in accordance
with
the
instructions
av
on
the
Lighting
and
Operating
plate
fastened
to
the
boiler.
P
SILENCE
•
The
pilot
is
located
under
the
boiler,
attached
7a,
"°
to
the
right
side
of
the
main
burner.
To
reach
a
TO
1)
pilot,
remove
outer
and
inner
combustion
cham,
4
c
ber
doors.
Be
sure
toreplace
combustion
cham-
TR2
NC
I
I
ber
doors
after
lighting
unit.
nAccougLE
a
ra
SEQUENCE
OF
OPERATION
(refer
to
wiring
dia-
'
j
gram,
fig.
10).
~MRI
a
SWITCH
a3
1.
For
initial
start-up,
the
system
is
electri-
runs
e"Es"su°as
cally
energized
by
closing
the
main
dis-
u
a,s,
au
TS"'Tc"
connect
switch
after
manual
ignition
of
Î PR2
WWGAS
I
I
pilot.
enessues
8
RA890 S
SWITCH
•
Panel
alarm
will
sound.
Move
alarm
sil-
sâ
MDICATOR
LAuP
ence
switch
on
control
box
to
the
OFF
s^rarvSuurosevALve
position'
OI
--rAcreaso
•
With
a proven
pilot
flame,
the
purge
timer
--Fiatowra'°
t
(S427B)
initiates
a
5
minute
prepurge
²
cycle.
At
the
end
of
the
prepurge
cycle,
the
TR1
contacts
open
and
TR2
contacts
aco
close.
The
alarm
silence
switch
may
now
be
moved
back
to
the
ON
position.
Alarm
F1GURE jo
should
remain
silent.
AOS
1Z9
AOS129·
13
Roenbeck
FILED: NEW YORK COUNTY CLERK 02/20/2018 10:20 AM
INDEX NO. 190311/2015
NYSCEF DOC. NO. 337
RECEIVED NYSCEF: 02/20/2018