Instruction manual SGS
49
is
Full-load measurement
10. From the service menu, select:
-
SERVICE OPERATION
|
FULL LOAD
-
Confirm with
.
The appliance is now in "FULL LOAD mode" and will ignite.
11. The appliance is now running at
FULL LOAD
. Read the value from the CO
2
meter and wait until this measured value has remained stable for some time.
This may take several minutes.
12. Then compare the measured CO
2
value against the value from the
table (3.4.3 "Gas data").
Caution
The CO
2
value at full load must be within ±1.0 vol% of the CO
2
value stated
in the table (3.4.3 "Gas data").
SGS 28 to 60
13. If necessary, adjust the CO
2
value using the adjuster screw until the value is
within the range listed in the table of CO
2
values.
Use the Allen key supplied for this. The key can be found in the plastic bag
that is attached to the appliance.
CO
2
adjustment (full load)
Note
Turning to the left (anticlockwise) means more gas (higher CO
2
level) and
turning to the right (clockwise) means less gas (lower CO
2
level).
Note
After conversion, you must check that the gas control valve is gastight.
14. If you have increased
Tset
, set it back to the original value using .
15. Continue with the CO
2
measurement under partial load.
SERVICE Ê Ê
FULL LOAD 65ÉC
Tset 70ÉC
RUNNING
IMD-1095b R0
Summary of Contents for SGS - 100
Page 7: ...4 Instruction manual SGS gis...
Page 11: ...Contents 8 Instruction manual SGS...
Page 23: ...Working principle of the water heater 20 Instruction manual SGS 2 gis...
Page 37: ...Installation types 34 Instruction manual SGS Installation 3...
Page 57: ...Conversion to a different gas category 54 Instruction manual SGS 4 is...
Page 65: ...Draining 62 Instruction manual SGS 6 gis...
Page 71: ...Status of the water heater 68 Instruction manual SGS 8 gis...
Page 75: ...Shutting down 72 Instruction manual SGS 10 gis...
Page 103: ...Service interval 100 Instruction manual SGS 14 is...
Page 112: ...Instruction manual SGS 109 is...
Page 119: ...Instruction manual SGS 116...