background image

ACGSS02307

Page 2 of 4

CATEGORY IV LISTED

• Requires AL29-4C gas tight rust resistant

venting material

PROFESSIONAL START-UP SERVICE

FURNISHED

• Assures optimum performance for each

installation

MEETS ASHRAE/IESNA 90.1-1999

5 YEAR HEAT EXCHANGER WARRANTY

• For complete information, consult written

warranty or contact A. O. Smith

OTHER VF

BOILER FEATURES:

• ASME 160# W.P.
• ASME PRESSURE RELIEF VALVE 125#
• FACTORY MOUNTED FLOW SWITCH
• MEETS CSD-1 CODE-–FACTORY STANDARD
• BRASS DRAIN VALVE
• LOW GAS PRESSURE SWITCH
• DIGITAL INLET/OUTLET  

TEMPERATURE READ OUT

• MANUAL RESET HI-LIMIT

• ALL BRONZE FACTORY MOUNTED PUMP

VF

BOILER APPROVED OPTIONS:

SEQUENCING PANEL 

ALARM BELL 

SIDEWALL VENT KITS  

VERTICAL AND HORIZONTAL 
DIRECT VENT KITS

SKID-MOUNTED SYSTEMS

DRY CONTACTS FOR ANY 
BOILER FAILURE

LOW WATER CUTOFF

LP GAS

CUPRO-NICKEL HEAT
EXCHANGER TUBES

Please consult latest edition of the Installation Manual for detailed venting information and 
maximum/minimum venting distances.

Model

No.

Input

Rating

Btu/hr

Water

Flow

Temperature Rise - °F (°C)

40

60

80

90

100

120

140

(22)

(33)

(44)

(90)

(56)

(67)

(78)

VW-500

500,000

GPH

1,268

845

634

563

507

423

362

LPH

4,797

3,198

2,399

2,132

1,919

1,599 1,371

VW-750

750,000

GPH

1,901

1,268

951

845

761

634

543

LPH

7,196

4,797

3,598

3,198

2,878

2,399 2,056

VW-1000 1,000,000

GPH

2,535

1,690

1,268

1,127

1,014

845

724

LPH

9,595

6,397

4,797

4,264

3,838

3,198 2,741

UP TO 88% EFFICIENT, HOT WATER SUPPLY BOILER WITH MODULATING FIRE 4:1 TURNDOWN

VERSATILE MULTI-VENTING CONFIGURATIONS

DIRECT-VENTING

SIDEWALL VENTING

CONVENTIONAL 
VENTING

NOTE:

Maximum gas supply pressure: 11˝ W.C. natural gas, 13.8˝ propane 

Minimum gas supply pressure: 4˝ W.C. natural gas, 8˝ propane

Electrical Power: 120 Volts, 60 Hertz, 30 Amps.

RECOVERY CAPACITIES

Reviews: