background image

Commercial Gas Boilers

 

ACMSS00507

Page 4 of 4

DUAL-ENERGY SOURCE OPTION

• Storage tanks can be specified with an optional

heat exchanger for winter heating using on-site
hydronic heating boiler(s), switching to domestic 
hot water boiler(s) for summertime operation

• Water-to-water or steam-to-water heat exchangers

available in single-wall or double-wall design

• Complete control packages can be factory-installed

for “hook up and run”  simplicity

PROFESSIONAL START-UP SERVICE FURNISHED

Assures optimum performance for each installation

MEETS ASHRAE/IESNA 90.1-1999

5 YEAR VF BOILER HEAT EXCHANGER WARRANTY

5 YEAR STORAGE TANK WARRANTY

For complete information, consult written warranty or

contact A. O. Smith

OTHER FEATURES:

ASME TEMPERATURE AND PRESSURE RELIEF

VALVE #125

TANK TEMPERATURE SENSOR AND

THERMOMETER

ISOLATION VALVES (BALL VALVES)

125 PSI TANK WORKING PRESSURE

ALL-BRONZE CIRCULATING PUMP

LARGE SYSTEMS SHIPPED WITH SPLIT/
BOLT TOGETHER SKIDS FOR EASE OF 
SHIPPING AND INSTALLATION

OTHER OPTIONS:

150 AND 160 PSI TANK WORKING PRESSURES

11˝ X 15˝ MANHOLES

Tank Type (A=Skid Mounted, J=Jacketed, V=Vertical, H= Horizontal)

TOTAL HOT WATER SUPPLY SYSTEM USING VF

BOILERS

SUGGESTED SPECIFICATION

Hot Water Supply System - shall consist of A. O. SMITH Ac-U-Temp factory assembled unit Model No. __________. System

shall be completely factory assembled and shall include the A.O. SMITH VF hot water supply boiler(s), with input 

of ____ BTU/H for (natural/propane) ____ gas and recovery capacity of _______ gph, and the A.O. SMITH glass-lined

(cement/epoxy) hot water storage tank with ____  gallons capacity for ________ mounting (vertical-horizontal). System 

shall include properly sized circulator, inlet and outlet thermometers, tank temperature thermometer, relief valve, and tank

temperature control. Entire system shall be rigidly mounted on welded steel skid base and shipped assembled to job site

(Ac-U-Temp systems employing tanks too large for shipping as an assembled unit, will be shipped with the tank mounted 

on a split bolt-together skid). See VF Boiler Specification Sheet for boiler details. See A.O.Smith Storage Specification 

sheets for storage tank details.

Hot water supply boiler(s) and storage tank(s) shall have a 5 year limited warranty against corrosion as outlined in the

written warranty

500 Tennessee Waltz Pkwy, Ashland City, TN 37015

For Technical Information and Automated Fax Service, call 800-527-1953.

A. O. Smith reserves the right to make product changes or improvements without prior notice.

©2007 A. O. Smith Corporation

Printed in U.S.A.

www.hotwater.com

Summary of Contents for VWT-1000

Page 1: ...ional vent or sealed combustion direct vent options For complete information on VF Hot Water Supply Boilers consult VF Specification Sheet GLASS LINED STORAGE TANKS Standard capacities up to 1 000 gallons Custom tanks available up to 10 000 gallons Standard tanks are factory jacketed and insulated bare uninsulated tanks also available Optional cement or epoxy lined tanks available For complete inf...

Page 2: ...7 57 2 6 4 6 4 AJV 500TA Inches 101 48 24 3 3 CM 256 5 121 9 61 6 4 6 4 AJV 500A Inches 86 54 25 1 5 3 3 CM 218 4 137 2 64 8 6 4 6 4 AJV 750A Inches 118 54 24 1 2 3 3 CM 299 7 137 2 62 2 6 4 6 4 AJV 1000A Inches 150 54 25 1 2 3 3 CM 381 137 2 64 8 6 4 6 4 BOILER DATA VERTICAL STORAGE VESSEL DATA MODEL NUMBER INCHES OR CM DIMENSIONS LENGTH A1 OUTLET DIM A2 WIDTH B1 HEIGHT B2 INLET HEIGHT B3 INLET S...

Page 3: ...standard available configurations Custom configurations designed to your specifications are available Contact your local A O Smith Sales Representative for assistance TOTAL HOT WATER SUPPLY SYSTEM USING VF BOILERS Configuration H Configuration P Configuration V ...

Page 4: ...SPECIFICATION Hot Water Supply System shall consist of A O SMITH Ac U Temp factory assembled unit Model No __________ System shall be completely factory assembled and shall include the A O SMITH VF hot water supply boiler s with input of ____ BTU H for natural propane ____ gas and recovery capacity of _______ gph and the A O SMITH glass lined cement epoxy hot water storage tank with ____ gallons c...

Reviews: