TDC-100 Series
AC Digital High-Resolution Controller
Installation & Maintenance Manual
10
07/24/20
www.atcontrols.com
IOM08032 REVISION 01
SPECIFICATIONS
POWER REQUIREMENTS
TDC-100: 117VAC
10%, 50/60 Hz
TDC-100A: 234VAC
10%, 50/60 Hz
TDC-100B: 24VAC
10%, 50/60 Hz
12 VA typical (not including output load)
Fuse Type: 6.3A TR5 Time Delay (replaceable)
COMMAND SIGNAL INPUT
Input Impedance
20K ohms (VOLTAGE CMD (+) Input)
251 ohms
1% (4-20 mA CMD (+) Input)
Loss of Command threshold
< 0.75V (1-5 VDC input)
< 1.5V (2-10 VDC input)
< 3mA (4-20mA input)
Command Out of Range threshold
> 5.25V (0-5 VDC, 1-5 VDC input)
> 10.5V (0-10 VDC, 2-10 VDC input)
> 21mA (4-20mA input)
FEEDBACK SIGNAL INPUT
Input Voltage: 0 to 2.5 VDC
External Feedback Potentiometer: 1K ohm
POWER SUPPLY OUTPUTS
+15V OUT (J2-8): 100mA maximum (not including option module)
+5V OUT (J2-7): 20mA maximum
NOTE:
Do not
connect these outputs to other power supplies.
AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60
C: 5A
ENVIRONMENTAL
Operating Temperature Range: 0
C to 60
C
Storage Temperature Range: -40
C to 85
C
Relative Humidity Range: 0 to 90 % (noncondensing)