UPS Edition One 1kVA, 2kVA, 3kVA
7. Specification
UPS Edition One
Model
1 kVA
2 kVA
3 kVA
Capacity
Phases
1:1
Capacity (KVA)
1
2
3
Capacity (W)
1000
2000
3000
Power factor output (cos phi)
1,0
Transfer time (ms)
Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms
Input
Rated voltage (V AC)
208 / 220 / 230 / 240
Voltage range (without battery) (V AC)
110~300 (176~264 @ 100%)
Frequency (Hz)
40~70
Power factor input
≥0.99
Nominal voltage (V DC)
24
48
72
Standard battery (pcs x Ah) (not included)
2 x 9
4 x 9
6 x 9
Charging current max (Default)
1
Output
Voltage (V AC)
208 / 220 / 230 / 240
Frequency (Hz)
Mains mode: 46~54Hz oder 56~64Hz,
Battery mode: (50/60±0.1%)Hz
Waveform
Pure Sinewave
Crest factor
3:1
Others
Dimensions (mm) w x d x h
144 x 399 x 209 191 x 460 x 337
Net weight (kg)
9,3
19,5
24,5
Noise level (dB (A))
<50 db 1 meter
Efficiency (%) AC-AC
88
90
90
Efficiency (%) DC-DC
85
Operating temperature
0°C~40°C
Storage temperature
-25°C~55°C
Relative humidity (non condensing)
20~90%
Installation height
< 1500m
IP rating
I
IEC/EN62040-1, IEC/EN60950-1
Standards
IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5, IEC61000-4-6, IEC61000-4-8