Ladespannungsparameter (Lithium)
operation manual
6.11 Charging modes
page 28
02/2022
12 / 24 / 36 / 48 V: 10 – 64 V (Standard: 29.4 V)
If the tolerance is greater than 0.2 V, the manufacturer assumes no liability for any
resulting system malfunctions.
12 / 24 / 36 / 48V: 9.2 - 63.8V (default: 28.7V)
LCD display charging mode
12 / 24 V: 9.2 - 31.8/ V (Standard: 14.0 V)
When the LCD display shows as left, press the MENU button for
one second, the gear icon will flash. Now you can set the
charging mode.
(Recovery voltage + 1.5V) ÿ Lithium overcharge protection voltage ÿ (Recovery
voltage + 0.2V).
1
DANGER:
0
WARNING:
Setting range of the charging voltage:
Dusk to Sunrise: The load output stays on from sunset to sunrise.
12 / 24 V: 10 – 32 V (Standard: 14.4 V)
The solar charge controllers of the a-TroniX series are suitable for all types of lithium batteries.
When selecting the lithium battery type, the overcharge protection and recovery voltage of the
lithium battery can be set via RS485 interface or via Bluetooth App.
Out of range parameter settings are not supported.
Permanently on: The load output is permanently switched on.
Manual: The load output can be switched on and off by briefly
pressing the MENU button.
Recovery voltage adjustment range:
USE
The required accuracy of the BMS must be at least 0.2V.
2 3 4 5 6 7 8 9 Night: The load output stays on 2-9 hours after sunset.