18
9.6.2
OPERATION
BY
THERMOREGULATOR
WITH
PERIODIC
ACTIVATION
The
function
is
disabled
if
P17=
0
(default).
If
the
pump
is
set
in
operation
by
thermoregulator
(
P03
=
1
,
default),
it
will
be
activated
periodically
for
a
time
periode
defined
by
the
parameter
P17
(in
seconds)
after
a
counting
time
set
by
the
parameter
P16
(in
minutes),
activated
when
the
pump
is
turned
off
for
satisfied
thermoregulation.
In
the
case
of
the
activation
of
the
flowswitch
alarms
with
automatic
reset
the
pump
is
still
operating
even
if
the
compressor
is
off.
The
periodic
function
is
also
interrupted
in
the
case
of
the
intervention
of
the
antifreeze
thermoregulator
that
constrains
the
opeartion
of
the
pump.
9.6.3
CONTINUOUS
OPERATION
In
this
operating
mode,
enabled
if
P03=0
,
the
pump
is
always
turned
on.
It
turns
off
only
when
there
is
in
OFF
state
.
Summary of Contents for HPE Series
Page 21: ......
Page 29: ...28 ...
Page 31: ...30 16 WATER PUMP CURVES 16 1 MODELS HPE 06 09 16 2 MODELS HPE 12 15 ...
Page 34: ...33 19 3 HPE 12 15 IN OUT 1 M ...
Page 35: ...34 20 WIRING DIAGRAMS 20 1 MODELS HPE 06 09 ...
Page 36: ...35 20 2 MODEL HPE 12 ...
Page 37: ...36 20 3 MODEL HPE 15 ...
Page 43: ...NOTE ...
Page 44: ...NOTE ...
Page 45: ...NOTE ...
Page 46: ...NOTE ...
Page 47: ......