9
3. CONNECTION
3.1. Setting the weighing instrument and the AD-8923-CC
Set the following items so that the weighing instrument and the AD-8923-CC have the same value for
each item.
Item
Weighing instrument
AD-8923-CC
Baud rate
600, 1200, 2400*, 4800, 9600, 19200 bps
Data bits, parity
7 bits EVEN*
Stop bits
1 bit*
Terminator
<CR><LF>*
Data format
A&D standard format
−
Communication control
No RTS
/
CTS control
−
Data output mode
Stream mode
−
*
Factory setting for the AD-8923-CC. The factory setting for the weighing instruments is
the same unless otherwise specified.
3.2. Connecting the cables
Connect the cables using the connectors located on the rear of the AD-8923-CC.
Connection example to the AD-4212C and a PLC
Note
Be sure to ground the AD-4212C and the AD-8923-CC.
PLC
(CC-Link master station)
AD-8923-CC
RS-232C connector (D-Sub 9-pin)
Connect to the power supply
CC-Link connector (5-pin)
Ground
CC-Link network
CC-Link network
To other remote stations
such as the AD-8923-CC.
AD-4212C