21
Water Connection
Connect the supply and return water lines.
The connection size is listed on the unit rating
sheet, along with the designed volumetric
flow rate. The maximum operating pressure
for AAON LN Series units is 125 psi.
Mounting Isolation
For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Doors
Lockable access door is provided to the
compressor and control compartment. A
separate access door is also provided to the
pumping package compartment.
A light switch with service lights is provided
on the wall of the compressor and control
compartment.
End Flashing Installation
On all LN Series units the cabinet width will
overhang the shipping trailer on each side.
In order to secure and protect the unit during
transit the sheet metal end flashings have
been removed from the unit. The slot created
at the base of each end of the unit allows the
unit to set firmly on the trailer deck.
Sheet metal flashings are shipped loose with
the unit and once the unit is set into place the
flashings must be installed on each end of the
unit to complete the finished seal at the base.
The flashings are unit specific and designed
to cover the slot at each end of the unit to
prevent water run-off into the curb.
Failure to attach and seal the end of unit with
the flashings may result in water leakage into
the curb.
Figure 7 - Factory Supplied End Flashings
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used
with
R-410A
and
other
refrigerants, even in trace amounts, in
a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
The chiller must be operated only with
liquid flowing through the evaporators.
WARNING
Installing Contractor is responsible for
proper sealing of the water piping
entries into the unit Failure to seal the
entries may result in damage to the
unit and property.
CAUTION