15
handling damaged goods, repairs, and freight
claims: (918) 382-6450.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction traffic
and in the proper orientation as marked on the
packaging with all internal packaging in
place. Secure all loose-shipped items.
Chiller
Failure to observe the following instructions
will result in premature failure of your
system, and possible voiding of the warranty.
Never turn off the main power supply to the
unit, except for complete shutdown. When
power is cut off from the unit, any
compressors using crankcase heaters cannot
prevent refrigerant migration. This means the
compressor will cool down, and liquid
refrigerant
may
accumulate
in
the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored if liquid enters the
compressor.
Before unit operation, the main power switch
must be turned on for at least 24 hours for
units with compressor crankcase heaters.
This will give the crankcase heater time to
clear any liquid accumulation out of the
compressor before it is required to run.
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. All motors, to
include and not be limited to pump
motors and condenser fan motors,
should all be checked by a qualified
service technician at startup and any
wiring alteration should only be made
at the unit power connection.
CAUTION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit power
connection.
CAUTION
CRANKCASE HEATER
OPERATION
Units
may
be
equipped
with
compressor crankcase heaters, which
should be energized at least 24 hours
prior to cooling operation, to clear any
liquid
refrigerant
from
the
compressors.
CAUTION
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 3 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING