72
Capacity
Maintenance Instructions
To clean strainer remove the bottom plug and
pull out strainer.
Adjustment
To adjust pressure setting, loosen the lock nut
and turn the adjusting bolt clockwise to
increase pressure, counter clockwise to
decrease pressure.
Note:
Use a pressure gauge downstream to
adjust and verify the pressure setting.
Troubleshooting
High System Pressure
If the downstream system pressure is higher
than the set pressure under no flow
conditions, the cause could be thermal
expansion, pressure creep or dirt/debris on
the seat. Thermal expansion occurs whenever
water is heated in a closed system. The
system is closed when supply pressure
exceeds 150 psi, or a check valve or backflow
preventer is installed in the supply piping. To
determine if this is the result of thermal
expansion, try briefly opening the cold water
tap. If the
increased pressure is caused by
thermal expansion, the pressure will
immediately be relieved and the system will
return to the set pressure.
Dimensions-Weights:
Summary of Contents for LZ Series
Page 2: ......
Page 27: ...27 Figure 6 Concrete Pad Mounting with Dimensions Figure 7 LZ Base ...
Page 36: ...36 Figure 17 Typical Flue Vent Piping ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 95: ...95 Flo Trex Cross Section ...