78
significantly less than the nameplate head
value it is typically permissible to throttle the
discharge isolation valve until the actual
operating head is equal to the nameplate
value.
Any noise or vibration usually disappears.
The system designer or operator should be
made aware of this soon as some adjustment
may be required to the pump impeller
diameter or drive settings, if applicable, to
make the pump suitable for the system as
installed.
Check rotation arrow prior to operating the
unit. The rotation of all Vertical In-Line units
is “clockwise” when viewed from the drive
end. (Looking from on top of / behind the
motor)
General Care
Vertical In-Line pumps are built to operate
without periodic maintenance, other than
motor lubrication on larger units. A
systematic inspection made at regular
intervals, will ensure years of trouble-free
operation, giving special attention to the
following:
Keep unit clean
Keep moisture, refuse, dust or other loose
particles away from the pump and
ventilating openings of the motor.
Avoid operating the unit in overheated
surroundings (Above 100ºF/40ºC).
Any possibility of the unit starting while
being serviced must be eliminated.
If mechanical seal environmental accessories
are installed, ensure water is flowing through
the sight flow indicator and that filter
cartridges are replaced as recommended.
Lubrication
Pump
Lubrication is not required. There are no
bearings in the pump that need external
lubrication service.
Large Series split-coupled units are installed
with a shaft bushing located beneath the
impeller that is lubricated from the pump
discharge. This bearing is field removable for
service on the 20x20x19 size without
disturbing the motor or other major pump
components.
Motor
Follow
the
lubrication
procedures
recommended by the motor manufacturer.
Many small and medium sized motors are
permanently lubricated and need no added
lubrication. Generally if there are grease
fittings evident the motor needs periodic
lubrication, and if there are no grease fittings
evident, no periodic lubrication is required.
Check the lubrication instructions supplied
with the motor for the particular frame size
indicated on the motor nameplate.
Check
rotation
arrow
prior
to
operating the unit.
CAUTION
Electric
shock
hazard.
Before
attempting to perform any service or
maintenance
on
pumping
unit,
disconnect power source to the driver,
LOCK IT OFF and tag with the reason.