74
Air Seals
Four adjustable diameter seals are provided
on each cassette to minimize transfer of air
between the counter flowing airstreams.
To adjust diameter seals, loosen diameter
seal adjusting screws and back seals away
from wheel surface. Rotate wheel clockwise
until two opposing spokes are hidden behind
the bearing support beam. Using a folded
piece of paper as a feeler gauge, position
paper between the wheel surface and
diameter seals.
Adjust seals towards wheel surface until a
slight friction on the feeler gauge (paper) is
detected when gauge is moved along the
length of the spoke. Retighten adjusting
screws and recheck clearance with “feeler”
gauge.
Wheel Drive Components
The wheel drive motor bearings are pre-
lubricated and no further lubrication is
necessary.
The wheel drive pulley is secured to the
drive motor shaft by a combination of either
a key or D slot and set screw.
The set screw is secured with removable
locktite to prevent loosening. Annually
confirm set screw is secure. The wheel drive
belt is a urethane stretch belt designed to
provide constant tension through the life of
the belt. No adjustment is required. Inspect
the drive belt annually for proper tracking
and tension. A properly tensioned belt will
turn the wheel immediately after power is
applied with no visible slippage during start-
up.
Installation Considerations
Energy recovery cassettes are incorporated
within the design of packaged units,
packaged air handlers and energy recovery
ventilators. In each case, it is recommended
that
the
following
considerations
be
addressed:
Accessibility
The cassette and all its operative parts; i.e.:
motor, belt, pulley, bearings, seals and
energy transfer segments must be accessible
for service and maintenance. This design
requires that adequate clearance be provided
outside the enclosure.
Orientation & Support
The Energy Recovery Cassette may be
mounted in any orientation. However, Care
must be taken to make certain that the
cassette frame remains flat and the bearing
beams are not racked.
To verify, make certain that the distance
between wheel rim and bearing beam is the
same at each end of the bearing beam, to
within 1/4 of an inch (dimension A & B).
This amount of racking can be compensated
for by adjusting the diameter seals.
If greater than 1/4 inch (dimension C),
racking must be corrected to ensure that
drive belt will not disengage from wheel.
Do Not use acid based cleaners,
aromatic
solvents,
steam
or
temperatures in excess of 170°F;
damage to the wheel may occur!
CAUTION
Summary of Contents for M2 Series
Page 2: ......
Page 5: ...5 Split System Piping Diagrams 98 M2 Series Startup Form 115 Maintenance Log 121 ...
Page 35: ...35 Table 1 Electric and Gas Heating Capacities ...
Page 38: ...38 Figure 5 M2 Series Unit Four Point Lifting ...
Page 39: ...39 Figure 6 M2 Series Unit Eight Point Lifting ...
Page 58: ...58 Figure 32 Supply Fan Banding ...
Page 95: ...95 Figure 52 Filter Layout Viewed from the Upstream Side of the Cooling Coil ...
Page 98: ...98 Split System Piping Diagrams Figure 53 A C Split System Piping Suction Down ...
Page 99: ...99 Figure 54 A C Split System Piping Suction Up ...
Page 100: ...100 Figure 55 A C with LAC Split System Piping Suction Up ...
Page 101: ...101 Figure 56 A C with Modulating Hot Gas Reheat Split System Piping Suction Down ...
Page 102: ...102 Figure 57 A C with Modulating Hot Gas Reheat Split System Piping Suction Up ...
Page 103: ...103 Figure 58 A C with Hot Gas Bypass Split System Piping Suction Down ...
Page 104: ...104 Figure 59 A C with Hot Gas Bypass Split System Piping Suction Up ...
Page 107: ...107 Figure 62 Heat Pump Split System Piping Suction Down ...
Page 108: ...108 Figure 63 Heat Pump Split System Piping Suction Up ...
Page 109: ...109 Figure 64 Heat Pump with Modulating Hot Gas Reheat Split System Piping Suction Down ...
Page 110: ...110 Figure 65 Heat Pump with Modulating Hot Gas Reheat Split System Piping Suction Up ...
Page 111: ...111 Figure 66 Heat Pump with Hot Gas Bypass Split System Piping Suction Down ...
Page 112: ...112 Figure 67 Heat Pump with Hot Gas Bypass Split System Piping Suction Up ...